Cable Size Calculator
Choose IEC 60364 (Europe), BS 7671 (UK) or the NEC (USA); your region's standard is picked automatically. Current-carrying capacity, overload protection, voltage drop, short circuit and earth fault loop on one screen, plus harmonics and motor starting. No sign-up, free PDF report.
1Supply and load
2Run and voltage drop
3Cable and installation
4Protection, short circuit and earthing
5Advanced: parallel cables, existing cable, motor starting, energy
Size comparison
The selected size and its neighbours against every check. Click a row to check that size.
| Size | Iz (A) | Loading | ΔU | Start | Short circuit | Lmax fault | Loss | Result |
|---|
How voltage drop grows with run length, and how loaded the selected size is.
How to calculate cable size
The right cable size is not chosen on current alone. IEC 60364 requires that a cable does not overheat, keeps enough voltage at the far end, withstands a short circuit, and lets the protective device disconnect an earth fault in time. Below are the formula for each condition, the IEC 60364-5-52 ampacity tables, correction factors and examples verified with the tool.
The table current It is corrected for air/ground temperature, grouping, soil resistivity and harmonics: Iz = It·k1·k2·k3·kh ≥ IB.
IB ≤ In ≤ Iz and I2 ≤ 1.45·Iz (IEC 60364-4-43). With gG fuses I2 = 1.6·In, so the cable may go up a size.
With resistance and reactance: u = b·(R·cos φ + X·sin φ)·IB·L. For motors it is also checked with the starting current.
Thermal withstand k²S² ≥ I²t; in TN systems Zs·Ia ≤ U₀. Protective conductor (PE) per IEC 60364-5-54 Table 54.2.
Cable sizing in six steps
-
1
Find the design current
Three-phase IB = P / (√3·U·cos φ·η), single-phase IB = P / (U·cos φ·η), DC IB = P / U. For a motor use the nameplate current.
-
2
Choose the protective device
The first standard rating at or above IB (6, 10, 16, 20, 25, 32, 40, 50, 63 A …). The cable must carry this In.
-
3
Set the installation method and factors
Choose the method (A1…F) from Table B.52.1; take the temperature (k1), grouping (k2), soil (k3) and harmonic (kh) factors from the tables below.
-
4
Pick the size from the table
The first size with It ≥ In / (k1·k2·k3·kh).
-
5
Check voltage drop
If the drop exceeds the limit, increase the size. On long runs this step usually decides.
-
6
Verify short circuit and fault loop
S ≥ √(I²t)/k and L ≤ Lmax. If not met, increase the size, change the device or add an RCD.
Cable sizing formulas
| Quantity | Formula | Note |
|---|---|---|
| Corrected capacity | Iz = It·k1·k2·k3·kh·n | n: parallel cables per phase |
| Protection coordination | IB ≤ In ≤ Iz, I2 ≤ 1.45·Iz | IEC 60364-4-43 |
| Voltage drop (Annex G) | u = b·(ρ·L/S·cos φ + λ·L·sin φ)·IB | b = 1 three-phase (phase-neutral), 2 single-phase and DC; λ = 0.08 mΩ/m |
| Drop in percent | Δu = 100·u / U₀ | U₀: line-to-neutral voltage |
| Conductor temperature | θ = θa + (θmax − θa)·(IB/Iz)² | resistance at this temperature: R = R20·(1 + α·(θ − 20)) |
| Short-circuit withstand | k²·S² ≥ I²t → S ≥ Ik·√t / k | k: Cu PVC 115, Cu XLPE 143, Al PVC 76, Al XLPE 94 |
| Fault loop (TN) | Zs·Ia ≤ U₀ | Zs = Ze + (Rphase + RPE)·L |
| Maximum length (conventional) | Lmax = 0.8·U₀ / (Ia·(rfaz + rPE)) | r: Ω/m; when Ze is unknown |
| Protective conductor | S ≤ 16: SPE = S · 16 < S ≤ 35: 16 · S > 35: S/2 | IEC 60364-5-54 Tablo 54.2 |
| Cable loss | P = m·IB²·R·L | m = 3 three-phase, 2 single-phase and DC |
Cable size and ampacity table (IEC 60364-5-52)
Current-carrying capacity (A). Air 30 °C; ground 20 °C, 2.5 K·m/W, 0.7 m depth. Three loaded conductors: three-phase circuit; two loaded: single-phase and DC. These are the values the tool uses; for the final selection use the cable maker's data.
Copper · PVC 70 °C · 3 loaded conductors (three-phase)
| mm² | A1 | A2 | B1 | B2 | C | D1 | D2 | E | F |
|---|---|---|---|---|---|---|---|---|---|
| 1.5 | 13.5 | 13 | 15.5 | 15 | 17.5 | 18 | 19 | 18.5 | – |
| 2.5 | 18 | 17.5 | 21 | 20 | 24 | 24 | 24 | 25 | – |
| 4 | 24 | 23 | 28 | 27 | 32 | 30 | 33 | 34 | – |
| 6 | 31 | 29 | 36 | 34 | 41 | 38 | 41 | 43 | – |
| 10 | 42 | 39 | 50 | 46 | 57 | 50 | 54 | 60 | – |
| 16 | 56 | 52 | 68 | 62 | 76 | 64 | 70 | 80 | – |
| 25 | 73 | 68 | 89 | 80 | 96 | 82 | 92 | 101 | 110 |
| 35 | 89 | 83 | 110 | 99 | 119 | 98 | 110 | 126 | 137 |
| 50 | 108 | 99 | 134 | 118 | 144 | 116 | 130 | 153 | 167 |
| 70 | 136 | 125 | 171 | 149 | 184 | 143 | 162 | 196 | 216 |
| 95 | 164 | 150 | 207 | 179 | 223 | 169 | 193 | 238 | 264 |
| 120 | 188 | 172 | 239 | 206 | 259 | 192 | 220 | 276 | 308 |
| 150 | 216 | 196 | 262 | 225 | 299 | 217 | 246 | 319 | 356 |
| 185 | 245 | 223 | 296 | 255 | 341 | 243 | 278 | 364 | 409 |
| 240 | 286 | 261 | 346 | 297 | 403 | 280 | 320 | 430 | 485 |
| 300 | 328 | 298 | 394 | 339 | 464 | 316 | 359 | 497 | 561 |
| 400 | – | – | – | – | – | – | – | – | 656 |
| 500 | – | – | – | – | – | – | – | – | 749 |
| 630 | – | – | – | – | – | – | – | – | 855 |
Copper · PVC 70 °C · 2 loaded conductors (single-phase, DC)
| mm² | A1 | A2 | B1 | B2 | C | D1 | D2 | E | F |
|---|---|---|---|---|---|---|---|---|---|
| 1.5 | 14.5 | 14 | 17.5 | 16.5 | 19.5 | 22 | 22 | 22 | – |
| 2.5 | 19.5 | 18.5 | 24 | 23 | 27 | 29 | 28 | 30 | – |
| 4 | 26 | 25 | 32 | 30 | 36 | 37 | 38 | 40 | – |
| 6 | 34 | 32 | 41 | 38 | 46 | 46 | 48 | 51 | – |
| 10 | 46 | 43 | 57 | 52 | 63 | 60 | 64 | 70 | – |
| 16 | 61 | 57 | 76 | 69 | 85 | 78 | 83 | 94 | – |
| 25 | 80 | 75 | 101 | 90 | 112 | 99 | 110 | 119 | 131 |
| 35 | 99 | 92 | 125 | 111 | 138 | 119 | 132 | 148 | 162 |
| 50 | 119 | 110 | 151 | 133 | 168 | 140 | 156 | 180 | 196 |
| 70 | 151 | 139 | 192 | 168 | 213 | 173 | 192 | 232 | 251 |
| 95 | 182 | 167 | 232 | 201 | 258 | 204 | 230 | 282 | 304 |
| 120 | 210 | 192 | 269 | 232 | 299 | 231 | 261 | 328 | 352 |
| 150 | 240 | 219 | 300 | 258 | 344 | 261 | 293 | 379 | 406 |
| 185 | 273 | 248 | 341 | 294 | 392 | 292 | 331 | 434 | 463 |
| 240 | 321 | 291 | 400 | 344 | 461 | 336 | 382 | 514 | 546 |
| 300 | 367 | 334 | 458 | 394 | 530 | 379 | 427 | 593 | 629 |
| 400 | – | – | – | – | – | – | – | – | 754 |
| 500 | – | – | – | – | – | – | – | – | 868 |
| 630 | – | – | – | – | – | – | – | – | 1005 |
Copper · XLPE / EPR 90 °C · 3 loaded conductors (three-phase)
| mm² | A1 | A2 | B1 | B2 | C | D1 | D2 | E | F |
|---|---|---|---|---|---|---|---|---|---|
| 1.5 | 17 | 16.5 | 20 | 19.5 | 22 | 21 | 23 | 23 | – |
| 2.5 | 23 | 22 | 28 | 26 | 30 | 28 | 30 | 32 | – |
| 4 | 31 | 30 | 37 | 35 | 40 | 36 | 39 | 42 | – |
| 6 | 40 | 38 | 48 | 44 | 52 | 44 | 49 | 54 | – |
| 10 | 54 | 51 | 66 | 60 | 71 | 58 | 65 | 75 | – |
| 16 | 73 | 68 | 88 | 80 | 96 | 75 | 84 | 100 | – |
| 25 | 95 | 89 | 117 | 105 | 119 | 96 | 107 | 127 | 135 |
| 35 | 117 | 109 | 144 | 128 | 147 | 115 | 129 | 158 | 169 |
| 50 | 141 | 130 | 175 | 154 | 179 | 135 | 153 | 192 | 207 |
| 70 | 179 | 164 | 222 | 194 | 229 | 167 | 188 | 246 | 268 |
| 95 | 216 | 197 | 269 | 233 | 278 | 197 | 226 | 298 | 328 |
| 120 | 249 | 227 | 312 | 268 | 322 | 223 | 257 | 346 | 383 |
| 150 | 285 | 259 | 342 | 300 | 371 | 251 | 287 | 399 | 444 |
| 185 | 324 | 295 | 384 | 340 | 424 | 281 | 324 | 456 | 510 |
| 240 | 380 | 346 | 450 | 398 | 500 | 324 | 375 | 538 | 607 |
| 300 | 435 | 396 | 514 | 455 | 576 | 365 | 419 | 621 | 703 |
| 400 | – | – | – | – | – | – | – | – | 823 |
| 500 | – | – | – | – | – | – | – | – | 946 |
| 630 | – | – | – | – | – | – | – | – | 1088 |
Copper · XLPE / EPR 90 °C · 2 loaded conductors (single-phase, DC)
| mm² | A1 | A2 | B1 | B2 | C | D1 | D2 | E | F |
|---|---|---|---|---|---|---|---|---|---|
| 1.5 | 19 | 18.5 | 23 | 22 | 24 | 25 | 27 | 26 | – |
| 2.5 | 26 | 25 | 31 | 30 | 33 | 33 | 35 | 36 | – |
| 4 | 35 | 33 | 42 | 40 | 45 | 43 | 46 | 49 | – |
| 6 | 45 | 42 | 54 | 51 | 58 | 53 | 58 | 63 | – |
| 10 | 61 | 57 | 75 | 69 | 80 | 71 | 77 | 86 | – |
| 16 | 81 | 76 | 100 | 91 | 107 | 91 | 100 | 115 | – |
| 25 | 106 | 99 | 133 | 119 | 138 | 116 | 129 | 149 | 161 |
| 35 | 131 | 121 | 164 | 146 | 171 | 139 | 155 | 185 | 200 |
| 50 | 158 | 145 | 198 | 175 | 209 | 164 | 183 | 225 | 242 |
| 70 | 200 | 183 | 253 | 221 | 269 | 203 | 225 | 289 | 310 |
| 95 | 241 | 220 | 306 | 265 | 328 | 239 | 270 | 352 | 377 |
| 120 | 278 | 253 | 354 | 305 | 382 | 271 | 306 | 410 | 437 |
| 150 | 318 | 290 | 393 | 334 | 441 | 306 | 343 | 473 | 504 |
| 185 | 362 | 329 | 449 | 384 | 506 | 343 | 387 | 542 | 575 |
| 240 | 424 | 386 | 528 | 459 | 599 | 395 | 448 | 641 | 679 |
| 300 | 486 | 442 | 603 | 532 | 693 | 446 | 502 | 741 | 783 |
| 400 | – | – | – | – | – | – | – | – | 940 |
| 500 | – | – | – | – | – | – | – | – | 1083 |
| 630 | – | – | – | – | – | – | – | – | 1254 |
Aluminium · PVC 70 °C · 3 loaded conductors (three-phase)
| mm² | A1 | A2 | B1 | B2 | C | D1 | D2 | E | F |
|---|---|---|---|---|---|---|---|---|---|
| 2.5 | 14 | 13.5 | 16.5 | 15.5 | 18.5 | 18.5 | – | 19.5 | – |
| 4 | 18.5 | 17.5 | 22 | 21 | 25 | 24 | – | 26 | – |
| 6 | 24 | 23 | 28 | 27 | 32 | 30 | – | 33 | – |
| 10 | 32 | 31 | 39 | 36 | 44 | 39 | – | 46 | – |
| 16 | 43 | 41 | 53 | 48 | 59 | 50 | 53 | 61 | – |
| 25 | 57 | 53 | 70 | 62 | 73 | 64 | 69 | 78 | 84 |
| 35 | 70 | 65 | 86 | 77 | 90 | 77 | 83 | 96 | 105 |
| 50 | 84 | 78 | 104 | 92 | 110 | 91 | 99 | 117 | 128 |
| 70 | 107 | 98 | 133 | 116 | 140 | 112 | 122 | 150 | 166 |
| 95 | 129 | 118 | 161 | 139 | 170 | 132 | 148 | 183 | 203 |
| 120 | 149 | 135 | 186 | 160 | 197 | 150 | 169 | 212 | 237 |
| 150 | 170 | 155 | 204 | 176 | 227 | 169 | 189 | 245 | 274 |
| 185 | 194 | 176 | 230 | 199 | 259 | 190 | 214 | 280 | 315 |
| 240 | 227 | 207 | 269 | 232 | 305 | 218 | 250 | 330 | 375 |
| 300 | 261 | 237 | 306 | 265 | 351 | 247 | 282 | 381 | 434 |
| 400 | – | – | – | – | – | – | – | – | 526 |
| 500 | – | – | – | – | – | – | – | – | 610 |
| 630 | – | – | – | – | – | – | – | – | 711 |
Aluminium · PVC 70 °C · 2 loaded conductors (single-phase, DC)
| mm² | A1 | A2 | B1 | B2 | C | D1 | D2 | E | F |
|---|---|---|---|---|---|---|---|---|---|
| 2.5 | 15 | 14.5 | 18.5 | 17.5 | 21 | 22 | – | 23 | – |
| 4 | 20 | 19.5 | 25 | 24 | 28 | 29 | – | 31 | – |
| 6 | 26 | 25 | 32 | 30 | 36 | 36 | – | 39 | – |
| 10 | 36 | 33 | 44 | 41 | 49 | 47 | – | 54 | – |
| 16 | 48 | 44 | 60 | 54 | 66 | 61 | 63 | 73 | – |
| 25 | 63 | 58 | 79 | 71 | 83 | 77 | 82 | 89 | 98 |
| 35 | 77 | 71 | 97 | 86 | 103 | 93 | 98 | 111 | 122 |
| 50 | 93 | 86 | 118 | 104 | 125 | 109 | 117 | 135 | 149 |
| 70 | 118 | 108 | 150 | 131 | 160 | 135 | 145 | 173 | 192 |
| 95 | 142 | 130 | 181 | 157 | 195 | 159 | 173 | 210 | 235 |
| 120 | 164 | 150 | 210 | 181 | 226 | 180 | 200 | 244 | 273 |
| 150 | 189 | 172 | 234 | 201 | 261 | 204 | 224 | 282 | 316 |
| 185 | 215 | 195 | 266 | 230 | 298 | 228 | 255 | 322 | 363 |
| 240 | 252 | 229 | 312 | 269 | 352 | 262 | 298 | 380 | 430 |
| 300 | 289 | 263 | 358 | 308 | 406 | 296 | 336 | 439 | 497 |
| 400 | – | – | – | – | – | – | – | – | 600 |
| 500 | – | – | – | – | – | – | – | – | 694 |
| 630 | – | – | – | – | – | – | – | – | 808 |
Aluminium · XLPE / EPR 90 °C · 3 loaded conductors (three-phase)
| mm² | A1 | A2 | B1 | B2 | C | D1 | D2 | E | F |
|---|---|---|---|---|---|---|---|---|---|
| 2.5 | 19 | 18 | 22 | 21 | 24 | 22 | – | 24 | – |
| 4 | 25 | 24 | 29 | 28 | 32 | 28 | – | 32 | – |
| 6 | 32 | 31 | 38 | 35 | 41 | 35 | – | 42 | – |
| 10 | 44 | 41 | 52 | 48 | 57 | 46 | – | 58 | – |
| 16 | 58 | 55 | 71 | 64 | 76 | 59 | 64 | 77 | – |
| 25 | 76 | 71 | 93 | 84 | 90 | 75 | 82 | 97 | 103 |
| 35 | 94 | 87 | 116 | 103 | 112 | 90 | 98 | 120 | 129 |
| 50 | 113 | 104 | 140 | 124 | 136 | 106 | 117 | 146 | 159 |
| 70 | 142 | 131 | 179 | 156 | 174 | 130 | 144 | 187 | 206 |
| 95 | 171 | 157 | 217 | 188 | 211 | 154 | 172 | 227 | 253 |
| 120 | 197 | 180 | 251 | 216 | 245 | 174 | 197 | 263 | 296 |
| 150 | 226 | 206 | 267 | 240 | 283 | 197 | 220 | 304 | 343 |
| 185 | 256 | 233 | 300 | 272 | 323 | 220 | 250 | 347 | 395 |
| 240 | 300 | 273 | 351 | 318 | 382 | 253 | 290 | 409 | 471 |
| 300 | 344 | 313 | 402 | 364 | 440 | 286 | 326 | 471 | 547 |
| 400 | – | – | – | – | – | – | – | – | 663 |
| 500 | – | – | – | – | – | – | – | – | 770 |
| 630 | – | – | – | – | – | – | – | – | 899 |
Aluminium · XLPE / EPR 90 °C · 2 loaded conductors (single-phase, DC)
| mm² | A1 | A2 | B1 | B2 | C | D1 | D2 | E | F |
|---|---|---|---|---|---|---|---|---|---|
| 2.5 | 20 | 19.5 | 25 | 23 | 26 | 26 | – | 28 | – |
| 4 | 27 | 26 | 33 | 31 | 35 | 33 | – | 38 | – |
| 6 | 35 | 33 | 43 | 40 | 45 | 42 | – | 49 | – |
| 10 | 48 | 45 | 59 | 54 | 62 | 55 | – | 67 | – |
| 16 | 64 | 60 | 79 | 72 | 84 | 71 | 76 | 91 | – |
| 25 | 84 | 78 | 105 | 94 | 101 | 90 | 98 | 108 | 121 |
| 35 | 103 | 96 | 130 | 115 | 126 | 108 | 117 | 135 | 150 |
| 50 | 125 | 115 | 157 | 138 | 154 | 128 | 139 | 164 | 184 |
| 70 | 158 | 145 | 200 | 175 | 198 | 158 | 170 | 211 | 237 |
| 95 | 191 | 175 | 242 | 210 | 241 | 186 | 204 | 257 | 289 |
| 120 | 220 | 201 | 281 | 242 | 280 | 211 | 233 | 300 | 337 |
| 150 | 253 | 230 | 307 | 261 | 324 | 238 | 261 | 346 | 389 |
| 185 | 288 | 262 | 351 | 300 | 371 | 267 | 296 | 397 | 447 |
| 240 | 338 | 307 | 412 | 358 | 439 | 307 | 343 | 470 | 530 |
| 300 | 387 | 352 | 471 | 415 | 508 | 346 | 386 | 543 | 613 |
| 400 | – | – | – | – | – | – | – | – | 740 |
| 500 | – | – | – | – | – | – | – | – | 856 |
| 630 | – | – | – | – | – | – | – | – | 996 |
A1–D2: Tables B.52.2–B.52.5; E and F (free air, perforated tray): Tables B.52.8–B.52.13. Method letters match the drawings in the calculator.
Correction factors
| °C | PVC | XLPE |
|---|---|---|
| 10 | 1.22 | 1.15 |
| 15 | 1.17 | 1.12 |
| 20 | 1.12 | 1.08 |
| 25 | 1.06 | 1.04 |
| 30 | 1.00 | 1.00 |
| 35 | 0.94 | 0.96 |
| 40 | 0.87 | 0.91 |
| 45 | 0.79 | 0.87 |
| 50 | 0.71 | 0.82 |
| 55 | 0.61 | 0.76 |
| 60 | 0.50 | 0.71 |
| °C | PVC | XLPE | K·m/W | D1 | D2 |
|---|---|---|---|---|---|
| 10 | 1.10 | 1.07 | 0.5 | 1.28 | 1.88 |
| 15 | 1.05 | 1.04 | 0.7 | 1.20 | 1.62 |
| 20 | 1.00 | 1.00 | 1.0 | 1.18 | 1.50 |
| 25 | 0.95 | 0.96 | 1.5 | 1.10 | 1.28 |
| 30 | 0.89 | 0.93 | 2.0 | 1.05 | 1.12 |
| 35 | 0.84 | 0.89 | 2.5 | 1.00 | 1.00 |
| 40 | 0.77 | 0.85 | 3.0 | 0.96 | 0.90 |
| Arrangement | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 12 | 16 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Bunched, in conduit or trunking | 1.00 | 0.80 | 0.70 | 0.65 | 0.60 | 0.57 | 0.54 | 0.52 | 0.50 | 0.45 | 0.41 | 0.38 |
| Single layer on wall, floor or unperforated tray | 1.00 | 0.85 | 0.79 | 0.75 | 0.73 | 0.72 | 0.72 | 0.71 | 0.70 | – | – | – |
| Single layer under a ceiling | 0.95 | 0.81 | 0.72 | 0.68 | 0.66 | 0.64 | 0.63 | 0.62 | 0.61 | – | – | – |
| Single layer on perforated tray | 1.00 | 0.88 | 0.82 | 0.77 | 0.75 | 0.73 | 0.73 | 0.72 | 0.72 | – | – | – |
| Single layer on ladder or cleats | 1.00 | 0.87 | 0.82 | 0.80 | 0.80 | 0.79 | 0.79 | 0.78 | 0.78 | – | – | – |
Single-layer arrangements have no further reduction beyond 9 circuits. Buried grouping (B.52.18 direct, B.52.19 in ducts) depends on spacing and is selected separately in the tool. Annex E: 3rd harmonic 15–33 % → 0.86; 33–45 % → on neutral current, 0.86; above 45 % → on neutral current, 1.00.
IEC 60364 vs BS 7671 vs NEC
The tool calculates all three standards and picks one for your region (United Kingdom → BS 7671, USA → NEC, elsewhere → IEC 60364). The idea is the same: the cable must not overheat, the voltage must hold up, it must survive a short circuit and a fault must be cleared quickly. The tables, factors and protection rules differ, so the same load can come out one size apart.
| IEC 60364-5-52 | BS 7671:2018+A4 | NEC (NFPA 70) 2023 | |
|---|---|---|---|
| Where | Europe (HD 60364: DIN VDE 0100, NF C 15-100 and others) and most countries | United Kingdom | USA; Canada (CSA C22.1) and Mexico (NOM-001-SEDE) are close to the NEC |
| Conductor size | mm² | mm² | AWG / kcmil |
| Ampacity table | Annex B, Tables B.52.2–B.52.13 | Appendix 4, Tables 4D1A–4E4A, 4D5 (T&E) | Table 310.16 (raceway, cable, earth), 310.17 (free air) |
| Reference temperature | Air 30 °C, ground 20 °C | Air 30 °C, ground 20 °C | 30 °C (86 °F) |
| Corrections | Temperature k₁, grouping k₂, soil k₃, harmonics | Ca, Cg, thermal insulation Ci, buried Cc, BS 3036 Cf = 0.725 | Ambient 310.15(B)(1), conductor count 310.15(C)(1), terminals 110.14(C) |
| Protection | IB ≤ In ≤ Iz, I2 ≤ 1.45·Iz | IB ≤ In ≤ Iz, I2 ≤ 1.45·Iz | 240.4 (next size up ≤ 800 A), 240.4(D) small conductors, 125 % for continuous load |
| Voltage drop | Annex G: 3 % lighting, 5 % other (recommended) | Appendix 4 Table 4Ab: 3 % lighting, 5 % other | Informational note: 3 % branch, 5 % feeder + branch |
| Fault protection | Zs·Ia ≤ U₀ | Zs ≤ Tables 41.2–41.4 (Cmin 0.95) | No Zs table; effective ground-fault path 250.4(A)(5) |
| Protective conductor | PE, Table 54.2 | cpc, Table 54.7 | EGC, Table 250.122 |
NEC Table 310.16 ampacity chart
Allowable ampacity (A): not more than three current-carrying conductors in raceway, cable or earth, 30 °C (86 °F). The terminal limit (110.14(C)) and 240.4(D) small-conductor protection apply on top; the tool checks both.
Copper and aluminum, 60 / 75 / 90 °C
| Size | mm² | Copper | Aluminum | ||||
|---|---|---|---|---|---|---|---|
| 60 °C | 75 °C | 90 °C | 60 °C | 75 °C | 90 °C | ||
| 14 AWG | 2.08 | 15 | 20 | 25 | – | – | – |
| 12 AWG | 3.31 | 20 | 25 | 30 | 15 | 20 | 25 |
| 10 AWG | 5.26 | 30 | 35 | 40 | 25 | 30 | 35 |
| 8 AWG | 8.37 | 40 | 50 | 55 | 35 | 40 | 45 |
| 6 AWG | 13.3 | 55 | 65 | 75 | 40 | 50 | 55 |
| 4 AWG | 21.2 | 70 | 85 | 95 | 55 | 65 | 75 |
| 3 AWG | 26.7 | 85 | 100 | 115 | 65 | 75 | 85 |
| 2 AWG | 33.6 | 95 | 115 | 130 | 75 | 90 | 100 |
| 1 AWG | 42.4 | 110 | 130 | 145 | 85 | 100 | 115 |
| 1/0 AWG | 53.5 | 125 | 150 | 170 | 100 | 120 | 135 |
| 2/0 AWG | 67.4 | 145 | 175 | 195 | 115 | 135 | 150 |
| 3/0 AWG | 85 | 165 | 200 | 225 | 130 | 155 | 175 |
| 4/0 AWG | 107.2 | 195 | 230 | 260 | 150 | 180 | 205 |
| 250 kcmil | 127 | 215 | 255 | 290 | 170 | 205 | 230 |
| 300 kcmil | 152 | 240 | 285 | 320 | 195 | 230 | 260 |
| 350 kcmil | 177 | 260 | 310 | 350 | 210 | 250 | 280 |
| 400 kcmil | 203 | 280 | 335 | 380 | 225 | 270 | 305 |
| 500 kcmil | 253 | 320 | 380 | 430 | 260 | 310 | 350 |
| 600 kcmil | 304 | 350 | 420 | 475 | 285 | 340 | 385 |
| 700 kcmil | 355 | 385 | 460 | 520 | 315 | 375 | 425 |
| 750 kcmil | 380 | 400 | 475 | 535 | 320 | 385 | 435 |
| 800 kcmil | 405 | 410 | 490 | 555 | 330 | 395 | 445 |
| 900 kcmil | 456 | 435 | 520 | 585 | 355 | 425 | 480 |
| 1000 kcmil | 507 | 455 | 545 | 615 | 375 | 445 | 500 |
| 1250 kcmil | 633 | 495 | 590 | 665 | 405 | 485 | 545 |
| 1500 kcmil | 760 | 525 | 625 | 705 | 435 | 520 | 585 |
| 1750 kcmil | 887 | 545 | 650 | 735 | 455 | 545 | 615 |
| 2000 kcmil | 1013 | 555 | 665 | 750 | 470 | 560 | 630 |
BS 7671 Table 4D5: twin and earth cable ratings
70 °C thermoplastic flat cable with protective conductor (6242Y), single-phase; air 30 °C. Methods 100–103 cover insulated ceilings and stud walls.
| mm² | Method 100 | Method 101 | Method 102 | Method 103 | C | A | mV/A/m | cpc |
|---|---|---|---|---|---|---|---|---|
| 1 | 13 | 10.5 | 13 | 8 | 16 | 11.5 | 44 | 1 |
| 1.5 | 16 | 13 | 16 | 10 | 20 | 14.5 | 29 | 1 |
| 2.5 | 21 | 17 | 21 | 13.5 | 27 | 20 | 18 | 1.5 |
| 4 | 27 | 22 | 27 | 18.5 | 37 | 26 | 11 | 1.5 |
| 6 | 34 | 27 | 35 | 23.5 | 47 | 32 | 7.3 | 2.5 |
| 10 | 45 | 36 | 47 | 32 | 64 | 44 | 4.4 | 4 |
| 16 | 57 | 46 | 63 | 42.5 | 85 | 57 | 2.8 | 6 |
Worked cable sizing examples
Entering the same values in the tool gives the same results; each example link opens the tool with those values.
| Example | Inputs | Result | Governed by |
|---|---|---|---|
| Motor feeder, direct-on-line | 22 kW, 400 V, cos φ 0.86, η 0.92 → I_B 40.1 A · 80 m · Cu PVC clipped direct (C) · MCB C 50 A · 5 % | 3×10 + PE 10 mm² | Overload protection (50 A) and fault loop (L_max 81 m). ΔU 2.50 %, 6.2 % at start. |
| Single-phase socket circuit | 230 V, 16 A · 35 m · Cu PVC in conduit on wall (B2) · MCB B 16 A · 3 % | 2×4 + PE 4 mm² | Voltage drop: 2.5 mm² carried the current, but at 35 m the drop exceeded 3 % (4 mm²: 2.09 %). |
| 24 V DC run | 20 A · 10 m · Cu PVC clipped direct (C) · 3 % (0.72 V) | 2×16 mm² | Voltage drop: 2.5 mm² was enough for current, but low voltage pushed it to 16 mm² (ΔU 0.48 V). |
| Main feeder, copper | 400 V, 250 A · 120 m · Cu XLPE on perforated tray (E) · MCCB 250 A, 10×I_n · 15 kA, 0.02 s | 3×120 + PE 70 mm² | Voltage drop and fault loop. I_z 346 A, ΔU 2.51 %, short circuit needs at least 14.8 mm². |
| Same feeder, aluminium | Same inputs, aluminium conductor | 3×185 + PE 95 mm² | Aluminium is two sizes larger (ΔU 2.66 %); short circuit needs at least 22.6 mm² (k = 94). |
| LED lighting board with harmonics | 400 V, 63 A · 50 m · 4-core Cu PVC on perforated tray (E) · 3rd harmonic 40 % · MCB C 63 A | 4×25 + PE 16 mm² | Neutral current 3·0.40·63 = 75.6 A > phase current: size chosen on the neutral with factor 0.86. Without harmonics 4×16 mm² would do. |
| Pump on a drive, buried | 75 kW, cos φ 0.95, η 0.95 → I_B 119.9 A · 300 m · Cu XLPE direct in ground (D2) · MCCB 125 A, 10×I_n · 5 % | 3×150 + PE 95 mm² | Fault loop: the drop was fine at 2.31 %, but a 1250 A magnetic trip over 300 m needs 150 mm². A lower magnetic setting or an RCD allows a smaller size. |
Frequently asked questions
How is cable size calculated?
Under IEC 60364 the smallest size must meet several conditions at once: the corrected current-carrying capacity must cover the load current and the device rating (I_B ≤ I_n ≤ I_z), voltage drop must stay within the limit, the cable must withstand the fault energy (k²S² ≥ I²t), and in a TN system the earth fault loop impedance must let the device disconnect in time. The tool on this page checks all of them together and picks the smallest size that passes.
What voltage drop is acceptable?
IEC 60364-5-52 Annex G recommends 3 % for lighting and 5 % for other uses in installations supplied from the public LV network, and 6 % and 8 % where the installation has its own transformer. National rules and project specifications may be stricter; on long motor feeders also check the drop during starting.
How many amps can a 2.5 mm² cable carry?
Per the IEC 60364-5-52 tables at 30 °C, copper PVC 2.5 mm² with two loaded conductors carries 23 A in conduit on a wall (B2) and 27 A clipped direct (C); three-phase (three loaded conductors) gives 20 A and 24 A. Hot surroundings and other cables in the same route reduce it.
Why can the short-circuit check increase the size?
During a fault the cable heats until the device clears. If the conductor does not meet k²S² ≥ I²t the insulation is damaged (copper PVC k = 115, XLPE 143). With delayed breakers or high fault levels, small sizes can fail this check. For current-limiting MCBs and fuses use the maker's let-through I²t.
What is earth fault loop impedance and maximum length?
In a TN system an earth fault current returns through the phase conductor and the protective conductor (PE). The loop impedance Z_s must be low enough to pass the current that trips the device in time (I_a): Z_s·I_a ≤ U₀. For a 32 A type C MCB, I_a = 320 A; if a long run cannot pass it, increase the size, use a type B device or add an RCD.
How do harmonics affect cable size?
LED lighting, IT and single-phase electronic loads create 3rd harmonics that add up in the neutral. Per IEC 60364-5-52 Annex E, above 15 % the capacity of a 4-5 core cable is reduced by 0.86, and above 33 % the size is chosen on the neutral current (≈ 3·h·I). The tool includes this at no cost.
What is the difference between copper and aluminium cable?
Aluminium has about 1.6 times the resistance of copper, so the same current and voltage drop usually need one or two sizes larger, and its short-circuit factor is lower (76 for PVC). Aluminium is lighter and cheaper but needs suitable terminals and torque. In practice aluminium below 16 mm² is not used.
Is this result enough for the final design?
The tool applies the IEC 60364 method and the report can go in your project file, but it is still a preliminary sizing. For the final selection use the cable maker's ratings and resistances, the device's real curves, measured fault level and loop impedance, and national regulations.