Cable Size Calculator

Choose IEC 60364 (Europe), BS 7671 (UK) or the NEC (USA); your region's standard is picked automatically. Current-carrying capacity, overload protection, voltage drop, short circuit and earth fault loop on one screen, plus harmonics and motor starting. No sign-up, free PDF report.

IEC 60364 · BS 7671 · NEC mm² and AWG / kcmil Temperature · grouping · soil Harmonics Motor starting Check an existing cable PDF report
Ampacity tables, formulas and examples
Cable Sizing Explained: Voltage Drop, Ampacity and Short Circuit
The five checks, with a worked motor feeder example Video page (6:07)
Standard
Units

1Supply and load

System
V
If kW is motor shaft power, enter the nameplate efficiency.

2Run and voltage drop

m
Cable length from panel to load, not the round trip.
%

3Cable and installation

Conductor
Insulation
Insulation rating (Table 310.4(1))
Installation method (IEC 60364-5-52 Table B.52.1)
Reference installation method (BS 7671 Table 4A2)
Installation (NEC 310.16 / 310.17)
°C
Hottest point on the route; tables are at 30 °C (86 °F).
°C
Sets the resistance and reactance used for voltage drop.
Above 3 the 310.15(C)(1) factor applies. The grounding conductor does not count; the neutral counts with nonlinear loads.
Automatic: 60 °C (140 °F) column for circuits of 100 A or less, 75 °C (167 °F) above.
Length totally surrounded by thermal insulation (Table 52.2).
Loaded cables side by side, including this one.
%
LED lighting, IT and drive loads load the neutral (IEC 60364-5-52 Annex E).

4Protection, short circuit and earthing

A
Current that blows the fuse in 0.4 s / 5 s (maker's curve).
kA
s
≈0.02 s instantaneous; delay setting if selective.
A²s
For current-limiting MCBs / fuses the short-circuit check uses this value.
Ω
Leave blank to use the conventional 0.8·U₀ method.
Network operator's declared maximum: TN-C-S 0.35 Ω, TN-S 0.8 Ω.
5Advanced: parallel cables, existing cable, motor starting, energy
%
h
/kWh

Size comparison

The selected size and its neighbours against every check. Click a row to check that size.

Size Iz (A) Loading ΔU Start Short circuit Lmax fault Loss Result

Visual analysis

How voltage drop grows with run length, and how loaded the selected size is.

Live
Voltage drop vs run length (%)
Current capacity utilisation
Voltage drop–
Guide

How to calculate cable size

The right cable size is not chosen on current alone. IEC 60364 requires that a cable does not overheat, keeps enough voltage at the far end, withstands a short circuit, and lets the protective device disconnect an earth fault in time. Below are the formula for each condition, the IEC 60364-5-52 ampacity tables, correction factors and examples verified with the tool.

1 · Current-carrying capacity

The table current It is corrected for air/ground temperature, grouping, soil resistivity and harmonics: Iz = It·k1·k2·k3·kh ≥ IB.

2 · Overload protection

IB ≤ In ≤ Iz and I2 ≤ 1.45·Iz (IEC 60364-4-43). With gG fuses I2 = 1.6·In, so the cable may go up a size.

3 · Voltage drop

With resistance and reactance: u = b·(R·cos φ + X·sin φ)·IB·L. For motors it is also checked with the starting current.

4 · Short circuit and fault loop

Thermal withstand k²S² ≥ I²t; in TN systems Zs·Ia ≤ U₀. Protective conductor (PE) per IEC 60364-5-54 Table 54.2.

Cable sizing in six steps

  1. 1
    Find the design current

    Three-phase IB = P / (√3·U·cos φ·η), single-phase IB = P / (U·cos φ·η), DC IB = P / U. For a motor use the nameplate current.

  2. 2
    Choose the protective device

    The first standard rating at or above IB (6, 10, 16, 20, 25, 32, 40, 50, 63 A …). The cable must carry this In.

  3. 3
    Set the installation method and factors

    Choose the method (A1…F) from Table B.52.1; take the temperature (k1), grouping (k2), soil (k3) and harmonic (kh) factors from the tables below.

  4. 4
    Pick the size from the table

    The first size with It ≥ In / (k1·k2·k3·kh).

  5. 5
    Check voltage drop

    If the drop exceeds the limit, increase the size. On long runs this step usually decides.

  6. 6
    Verify short circuit and fault loop

    S ≥ √(I²t)/k and L ≤ Lmax. If not met, increase the size, change the device or add an RCD.

Cable sizing formulas

QuantityFormulaNote
Corrected capacity Iz = It·k1·k2·k3·kh·n n: parallel cables per phase
Protection coordination IB ≤ In ≤ Iz, I2 ≤ 1.45·Iz IEC 60364-4-43
Voltage drop (Annex G) u = b·(ρ·L/S·cos φ + λ·L·sin φ)·IB b = 1 three-phase (phase-neutral), 2 single-phase and DC; λ = 0.08 mΩ/m
Drop in percent Δu = 100·u / U₀ U₀: line-to-neutral voltage
Conductor temperature θ = θa + (θmax − θa)·(IB/Iz)² resistance at this temperature: R = R20·(1 + α·(θ − 20))
Short-circuit withstand k²·S² ≥ I²t → S ≥ Ik·√t / k k: Cu PVC 115, Cu XLPE 143, Al PVC 76, Al XLPE 94
Fault loop (TN) Zs·Ia ≤ U₀ Zs = Ze + (Rphase + RPE)·L
Maximum length (conventional) Lmax = 0.8·U₀ / (Ia·(rfaz + rPE)) r: Ω/m; when Ze is unknown
Protective conductor S ≤ 16: SPE = S · 16 < S ≤ 35: 16 · S > 35: S/2 IEC 60364-5-54 Tablo 54.2
Cable loss P = m·IB²·R·L m = 3 three-phase, 2 single-phase and DC

Cable size and ampacity table (IEC 60364-5-52)

Current-carrying capacity (A). Air 30 °C; ground 20 °C, 2.5 K·m/W, 0.7 m depth. Three loaded conductors: three-phase circuit; two loaded: single-phase and DC. These are the values the tool uses; for the final selection use the cable maker's data.

Copper · PVC 70 °C · 3 loaded conductors (three-phase)
mm² A1 A2 B1 B2 C D1 D2 E F
1.5 13.5 13 15.5 15 17.5 18 19 18.5 –
2.5 18 17.5 21 20 24 24 24 25 –
4 24 23 28 27 32 30 33 34 –
6 31 29 36 34 41 38 41 43 –
10 42 39 50 46 57 50 54 60 –
16 56 52 68 62 76 64 70 80 –
25 73 68 89 80 96 82 92 101 110
35 89 83 110 99 119 98 110 126 137
50 108 99 134 118 144 116 130 153 167
70 136 125 171 149 184 143 162 196 216
95 164 150 207 179 223 169 193 238 264
120 188 172 239 206 259 192 220 276 308
150 216 196 262 225 299 217 246 319 356
185 245 223 296 255 341 243 278 364 409
240 286 261 346 297 403 280 320 430 485
300 328 298 394 339 464 316 359 497 561
400 – – – – – – – – 656
500 – – – – – – – – 749
630 – – – – – – – – 855
Copper · PVC 70 °C · 2 loaded conductors (single-phase, DC)
mm² A1 A2 B1 B2 C D1 D2 E F
1.5 14.5 14 17.5 16.5 19.5 22 22 22 –
2.5 19.5 18.5 24 23 27 29 28 30 –
4 26 25 32 30 36 37 38 40 –
6 34 32 41 38 46 46 48 51 –
10 46 43 57 52 63 60 64 70 –
16 61 57 76 69 85 78 83 94 –
25 80 75 101 90 112 99 110 119 131
35 99 92 125 111 138 119 132 148 162
50 119 110 151 133 168 140 156 180 196
70 151 139 192 168 213 173 192 232 251
95 182 167 232 201 258 204 230 282 304
120 210 192 269 232 299 231 261 328 352
150 240 219 300 258 344 261 293 379 406
185 273 248 341 294 392 292 331 434 463
240 321 291 400 344 461 336 382 514 546
300 367 334 458 394 530 379 427 593 629
400 – – – – – – – – 754
500 – – – – – – – – 868
630 – – – – – – – – 1005
Copper · XLPE / EPR 90 °C · 3 loaded conductors (three-phase)
mm² A1 A2 B1 B2 C D1 D2 E F
1.5 17 16.5 20 19.5 22 21 23 23 –
2.5 23 22 28 26 30 28 30 32 –
4 31 30 37 35 40 36 39 42 –
6 40 38 48 44 52 44 49 54 –
10 54 51 66 60 71 58 65 75 –
16 73 68 88 80 96 75 84 100 –
25 95 89 117 105 119 96 107 127 135
35 117 109 144 128 147 115 129 158 169
50 141 130 175 154 179 135 153 192 207
70 179 164 222 194 229 167 188 246 268
95 216 197 269 233 278 197 226 298 328
120 249 227 312 268 322 223 257 346 383
150 285 259 342 300 371 251 287 399 444
185 324 295 384 340 424 281 324 456 510
240 380 346 450 398 500 324 375 538 607
300 435 396 514 455 576 365 419 621 703
400 – – – – – – – – 823
500 – – – – – – – – 946
630 – – – – – – – – 1088
Copper · XLPE / EPR 90 °C · 2 loaded conductors (single-phase, DC)
mm² A1 A2 B1 B2 C D1 D2 E F
1.5 19 18.5 23 22 24 25 27 26 –
2.5 26 25 31 30 33 33 35 36 –
4 35 33 42 40 45 43 46 49 –
6 45 42 54 51 58 53 58 63 –
10 61 57 75 69 80 71 77 86 –
16 81 76 100 91 107 91 100 115 –
25 106 99 133 119 138 116 129 149 161
35 131 121 164 146 171 139 155 185 200
50 158 145 198 175 209 164 183 225 242
70 200 183 253 221 269 203 225 289 310
95 241 220 306 265 328 239 270 352 377
120 278 253 354 305 382 271 306 410 437
150 318 290 393 334 441 306 343 473 504
185 362 329 449 384 506 343 387 542 575
240 424 386 528 459 599 395 448 641 679
300 486 442 603 532 693 446 502 741 783
400 – – – – – – – – 940
500 – – – – – – – – 1083
630 – – – – – – – – 1254
Aluminium · PVC 70 °C · 3 loaded conductors (three-phase)
mm² A1 A2 B1 B2 C D1 D2 E F
2.5 14 13.5 16.5 15.5 18.5 18.5 – 19.5 –
4 18.5 17.5 22 21 25 24 – 26 –
6 24 23 28 27 32 30 – 33 –
10 32 31 39 36 44 39 – 46 –
16 43 41 53 48 59 50 53 61 –
25 57 53 70 62 73 64 69 78 84
35 70 65 86 77 90 77 83 96 105
50 84 78 104 92 110 91 99 117 128
70 107 98 133 116 140 112 122 150 166
95 129 118 161 139 170 132 148 183 203
120 149 135 186 160 197 150 169 212 237
150 170 155 204 176 227 169 189 245 274
185 194 176 230 199 259 190 214 280 315
240 227 207 269 232 305 218 250 330 375
300 261 237 306 265 351 247 282 381 434
400 – – – – – – – – 526
500 – – – – – – – – 610
630 – – – – – – – – 711
Aluminium · PVC 70 °C · 2 loaded conductors (single-phase, DC)
mm² A1 A2 B1 B2 C D1 D2 E F
2.5 15 14.5 18.5 17.5 21 22 – 23 –
4 20 19.5 25 24 28 29 – 31 –
6 26 25 32 30 36 36 – 39 –
10 36 33 44 41 49 47 – 54 –
16 48 44 60 54 66 61 63 73 –
25 63 58 79 71 83 77 82 89 98
35 77 71 97 86 103 93 98 111 122
50 93 86 118 104 125 109 117 135 149
70 118 108 150 131 160 135 145 173 192
95 142 130 181 157 195 159 173 210 235
120 164 150 210 181 226 180 200 244 273
150 189 172 234 201 261 204 224 282 316
185 215 195 266 230 298 228 255 322 363
240 252 229 312 269 352 262 298 380 430
300 289 263 358 308 406 296 336 439 497
400 – – – – – – – – 600
500 – – – – – – – – 694
630 – – – – – – – – 808
Aluminium · XLPE / EPR 90 °C · 3 loaded conductors (three-phase)
mm² A1 A2 B1 B2 C D1 D2 E F
2.5 19 18 22 21 24 22 – 24 –
4 25 24 29 28 32 28 – 32 –
6 32 31 38 35 41 35 – 42 –
10 44 41 52 48 57 46 – 58 –
16 58 55 71 64 76 59 64 77 –
25 76 71 93 84 90 75 82 97 103
35 94 87 116 103 112 90 98 120 129
50 113 104 140 124 136 106 117 146 159
70 142 131 179 156 174 130 144 187 206
95 171 157 217 188 211 154 172 227 253
120 197 180 251 216 245 174 197 263 296
150 226 206 267 240 283 197 220 304 343
185 256 233 300 272 323 220 250 347 395
240 300 273 351 318 382 253 290 409 471
300 344 313 402 364 440 286 326 471 547
400 – – – – – – – – 663
500 – – – – – – – – 770
630 – – – – – – – – 899
Aluminium · XLPE / EPR 90 °C · 2 loaded conductors (single-phase, DC)
mm² A1 A2 B1 B2 C D1 D2 E F
2.5 20 19.5 25 23 26 26 – 28 –
4 27 26 33 31 35 33 – 38 –
6 35 33 43 40 45 42 – 49 –
10 48 45 59 54 62 55 – 67 –
16 64 60 79 72 84 71 76 91 –
25 84 78 105 94 101 90 98 108 121
35 103 96 130 115 126 108 117 135 150
50 125 115 157 138 154 128 139 164 184
70 158 145 200 175 198 158 170 211 237
95 191 175 242 210 241 186 204 257 289
120 220 201 281 242 280 211 233 300 337
150 253 230 307 261 324 238 261 346 389
185 288 262 351 300 371 267 296 397 447
240 338 307 412 358 439 307 343 470 530
300 387 352 471 415 508 346 386 543 613
400 – – – – – – – – 740
500 – – – – – – – – 856
630 – – – – – – – – 996

A1–D2: Tables B.52.2–B.52.5; E and F (free air, perforated tray): Tables B.52.8–B.52.13. Method letters match the drawings in the calculator.

Correction factors

Ambient temperature k₁ (air, B.52.14)
°CPVCXLPE
101.221.15
151.171.12
201.121.08
251.061.04
301.001.00
350.940.96
400.870.91
450.790.87
500.710.82
550.610.76
600.500.71
Ground temperature k₁ (B.52.15) and soil resistivity k₃ (B.52.16)
°CPVCXLPEK·m/WD1D2
101.101.07 0.51.281.88
151.051.04 0.71.201.62
201.001.00 1.01.181.50
250.950.96 1.51.101.28
300.890.93 2.01.051.12
350.840.89 2.51.001.00
400.770.85 3.00.960.90
Grouping factor k₂ (B.52.17) by number of circuits
Arrangement 1 2 3 4 5 6 7 8 9 12 16 20
Bunched, in conduit or trunking 1.00 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50 0.45 0.41 0.38
Single layer on wall, floor or unperforated tray 1.00 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70 – – –
Single layer under a ceiling 0.95 0.81 0.72 0.68 0.66 0.64 0.63 0.62 0.61 – – –
Single layer on perforated tray 1.00 0.88 0.82 0.77 0.75 0.73 0.73 0.72 0.72 – – –
Single layer on ladder or cleats 1.00 0.87 0.82 0.80 0.80 0.79 0.79 0.78 0.78 – – –

Single-layer arrangements have no further reduction beyond 9 circuits. Buried grouping (B.52.18 direct, B.52.19 in ducts) depends on spacing and is selected separately in the tool. Annex E: 3rd harmonic 15–33 % → 0.86; 33–45 % → on neutral current, 0.86; above 45 % → on neutral current, 1.00.

IEC 60364 vs BS 7671 vs NEC

The tool calculates all three standards and picks one for your region (United Kingdom → BS 7671, USA → NEC, elsewhere → IEC 60364). The idea is the same: the cable must not overheat, the voltage must hold up, it must survive a short circuit and a fault must be cleared quickly. The tables, factors and protection rules differ, so the same load can come out one size apart.

IEC 60364-5-52 BS 7671:2018+A4 NEC (NFPA 70) 2023
Where Europe (HD 60364: DIN VDE 0100, NF C 15-100 and others) and most countries United Kingdom USA; Canada (CSA C22.1) and Mexico (NOM-001-SEDE) are close to the NEC
Conductor size mm² mm² AWG / kcmil
Ampacity table Annex B, Tables B.52.2–B.52.13 Appendix 4, Tables 4D1A–4E4A, 4D5 (T&E) Table 310.16 (raceway, cable, earth), 310.17 (free air)
Reference temperature Air 30 °C, ground 20 °C Air 30 °C, ground 20 °C 30 °C (86 °F)
Corrections Temperature k₁, grouping k₂, soil k₃, harmonics Ca, Cg, thermal insulation Ci, buried Cc, BS 3036 Cf = 0.725 Ambient 310.15(B)(1), conductor count 310.15(C)(1), terminals 110.14(C)
Protection IB ≤ In ≤ Iz, I2 ≤ 1.45·Iz IB ≤ In ≤ Iz, I2 ≤ 1.45·Iz 240.4 (next size up ≤ 800 A), 240.4(D) small conductors, 125 % for continuous load
Voltage drop Annex G: 3 % lighting, 5 % other (recommended) Appendix 4 Table 4Ab: 3 % lighting, 5 % other Informational note: 3 % branch, 5 % feeder + branch
Fault protection Zs·Ia ≤ U₀ Zs ≤ Tables 41.2–41.4 (Cmin 0.95) No Zs table; effective ground-fault path 250.4(A)(5)
Protective conductor PE, Table 54.2 cpc, Table 54.7 EGC, Table 250.122

NEC Table 310.16 ampacity chart

Allowable ampacity (A): not more than three current-carrying conductors in raceway, cable or earth, 30 °C (86 °F). The terminal limit (110.14(C)) and 240.4(D) small-conductor protection apply on top; the tool checks both.

Copper and aluminum, 60 / 75 / 90 °C
Size mm² Copper Aluminum
60 °C 75 °C 90 °C 60 °C 75 °C 90 °C
14 AWG 2.08 15 20 25 – – –
12 AWG 3.31 20 25 30 15 20 25
10 AWG 5.26 30 35 40 25 30 35
8 AWG 8.37 40 50 55 35 40 45
6 AWG 13.3 55 65 75 40 50 55
4 AWG 21.2 70 85 95 55 65 75
3 AWG 26.7 85 100 115 65 75 85
2 AWG 33.6 95 115 130 75 90 100
1 AWG 42.4 110 130 145 85 100 115
1/0 AWG 53.5 125 150 170 100 120 135
2/0 AWG 67.4 145 175 195 115 135 150
3/0 AWG 85 165 200 225 130 155 175
4/0 AWG 107.2 195 230 260 150 180 205
250 kcmil 127 215 255 290 170 205 230
300 kcmil 152 240 285 320 195 230 260
350 kcmil 177 260 310 350 210 250 280
400 kcmil 203 280 335 380 225 270 305
500 kcmil 253 320 380 430 260 310 350
600 kcmil 304 350 420 475 285 340 385
700 kcmil 355 385 460 520 315 375 425
750 kcmil 380 400 475 535 320 385 435
800 kcmil 405 410 490 555 330 395 445
900 kcmil 456 435 520 585 355 425 480
1000 kcmil 507 455 545 615 375 445 500
1250 kcmil 633 495 590 665 405 485 545
1500 kcmil 760 525 625 705 435 520 585
1750 kcmil 887 545 650 735 455 545 615
2000 kcmil 1013 555 665 750 470 560 630

BS 7671 Table 4D5: twin and earth cable ratings

70 °C thermoplastic flat cable with protective conductor (6242Y), single-phase; air 30 °C. Methods 100–103 cover insulated ceilings and stud walls.

mm² Method 100 Method 101 Method 102 Method 103 C A mV/A/m cpc
1 13 10.5 13 8 16 11.5 44 1
1.5 16 13 16 10 20 14.5 29 1
2.5 21 17 21 13.5 27 20 18 1.5
4 27 22 27 18.5 37 26 11 1.5
6 34 27 35 23.5 47 32 7.3 2.5
10 45 36 47 32 64 44 4.4 4
16 57 46 63 42.5 85 57 2.8 6

Worked cable sizing examples

Entering the same values in the tool gives the same results; each example link opens the tool with those values.

Example Inputs Result Governed by
Motor feeder, direct-on-line 22 kW, 400 V, cos φ 0.86, η 0.92 → I_B 40.1 A · 80 m · Cu PVC clipped direct (C) · MCB C 50 A · 5 % 3×10 + PE 10 mm² Overload protection (50 A) and fault loop (L_max 81 m). ΔU 2.50 %, 6.2 % at start.
Single-phase socket circuit 230 V, 16 A · 35 m · Cu PVC in conduit on wall (B2) · MCB B 16 A · 3 % 2×4 + PE 4 mm² Voltage drop: 2.5 mm² carried the current, but at 35 m the drop exceeded 3 % (4 mm²: 2.09 %).
24 V DC run 20 A · 10 m · Cu PVC clipped direct (C) · 3 % (0.72 V) 2×16 mm² Voltage drop: 2.5 mm² was enough for current, but low voltage pushed it to 16 mm² (ΔU 0.48 V).
Main feeder, copper 400 V, 250 A · 120 m · Cu XLPE on perforated tray (E) · MCCB 250 A, 10×I_n · 15 kA, 0.02 s 3×120 + PE 70 mm² Voltage drop and fault loop. I_z 346 A, ΔU 2.51 %, short circuit needs at least 14.8 mm².
Same feeder, aluminium Same inputs, aluminium conductor 3×185 + PE 95 mm² Aluminium is two sizes larger (ΔU 2.66 %); short circuit needs at least 22.6 mm² (k = 94).
LED lighting board with harmonics 400 V, 63 A · 50 m · 4-core Cu PVC on perforated tray (E) · 3rd harmonic 40 % · MCB C 63 A 4×25 + PE 16 mm² Neutral current 3·0.40·63 = 75.6 A > phase current: size chosen on the neutral with factor 0.86. Without harmonics 4×16 mm² would do.
Pump on a drive, buried 75 kW, cos φ 0.95, η 0.95 → I_B 119.9 A · 300 m · Cu XLPE direct in ground (D2) · MCCB 125 A, 10×I_n · 5 % 3×150 + PE 95 mm² Fault loop: the drop was fine at 2.31 %, but a 1250 A magnetic trip over 300 m needs 150 mm². A lower magnetic setting or an RCD allows a smaller size.

Frequently asked questions

How is cable size calculated?

Under IEC 60364 the smallest size must meet several conditions at once: the corrected current-carrying capacity must cover the load current and the device rating (I_B ≤ I_n ≤ I_z), voltage drop must stay within the limit, the cable must withstand the fault energy (k²S² ≥ I²t), and in a TN system the earth fault loop impedance must let the device disconnect in time. The tool on this page checks all of them together and picks the smallest size that passes.

What voltage drop is acceptable?

IEC 60364-5-52 Annex G recommends 3 % for lighting and 5 % for other uses in installations supplied from the public LV network, and 6 % and 8 % where the installation has its own transformer. National rules and project specifications may be stricter; on long motor feeders also check the drop during starting.

How many amps can a 2.5 mm² cable carry?

Per the IEC 60364-5-52 tables at 30 °C, copper PVC 2.5 mm² with two loaded conductors carries 23 A in conduit on a wall (B2) and 27 A clipped direct (C); three-phase (three loaded conductors) gives 20 A and 24 A. Hot surroundings and other cables in the same route reduce it.

Why can the short-circuit check increase the size?

During a fault the cable heats until the device clears. If the conductor does not meet k²S² ≥ I²t the insulation is damaged (copper PVC k = 115, XLPE 143). With delayed breakers or high fault levels, small sizes can fail this check. For current-limiting MCBs and fuses use the maker's let-through I²t.

What is earth fault loop impedance and maximum length?

In a TN system an earth fault current returns through the phase conductor and the protective conductor (PE). The loop impedance Z_s must be low enough to pass the current that trips the device in time (I_a): Z_s·I_a ≤ U₀. For a 32 A type C MCB, I_a = 320 A; if a long run cannot pass it, increase the size, use a type B device or add an RCD.

How do harmonics affect cable size?

LED lighting, IT and single-phase electronic loads create 3rd harmonics that add up in the neutral. Per IEC 60364-5-52 Annex E, above 15 % the capacity of a 4-5 core cable is reduced by 0.86, and above 33 % the size is chosen on the neutral current (≈ 3·h·I). The tool includes this at no cost.

What is the difference between copper and aluminium cable?

Aluminium has about 1.6 times the resistance of copper, so the same current and voltage drop usually need one or two sizes larger, and its short-circuit factor is lower (76 for PVC). Aluminium is lighter and cheaper but needs suitable terminals and torque. In practice aluminium below 16 mm² is not used.

Is this result enough for the final design?

The tool applies the IEC 60364 method and the report can go in your project file, but it is still a preliminary sizing. For the final selection use the cable maker's ratings and resistances, the device's real curves, measured fault level and loop impedance, and national regulations.