Mode: Regeneration
Analog Outputs
The update time for analog outputs is 250μs; although the output will only change at the update time defined by the source parameter for the output. The following exceptions apply:
Analog Inputs
The normal update time for the analog inputs is 250us. If a thermistor mode is selected the update time is increased to 4ms. It is possible to insert a filter in each of the analogue inputs using Analog Input 1 Filter Time Constant (07.063) etc. to reduce the effect of noise on the input. Analog Input 1 Fast Update Active (07.026) and Analog Input 2 Fast Update Active (07.027) indicate if fast 250us updating is active for each input.
The diagram below shows the parameter structure for each I/O. See Internal I/O Identifier (11.068) for details of which I/O is present for different I/O options. Not all parameters shown in the diagam below are available in every drive derivative.
| Parameter | 07.003 Analog Input 3 | ||
|---|---|---|---|
| Short description | Displays the value of analog input 3 | ||
| Mode | Regeneration | ||
| Minimum | -100.00 | Maximum | 100.00 |
| Default | Units | % | |
| Type | 16 Bit Volatile | Update Rate | 250us write |
| Display Format | Standard | Decimal Places | 2 |
| Coding | RO, FI, ND, NC, PT | ||
Analog Input 3 (07.003) shows the level of analogue input 3.
| Parameter | 07.004 Monitored Temperature 1 | ||
|---|---|---|---|
| Short description | Displays the temperature set up by Temperature Monitor Select 1 | ||
| Mode | Regeneration | ||
| Minimum | -250 | Maximum | 250 |
| Default | Units | °C | |
| Type | 16 Bit Volatile | Update Rate | Background write |
| Display Format | Standard | Decimal Places | 0 |
| Coding | RO, ND, NC, PT | ||
Thermal monitoring is provided within the drive to protect the power stage and the control system from over temperature.
Monitored Temperature 1 (07.004), Monitored Temperature 2 (07.005) and Monitored Temperature 3 (07.006) give an indication of the temperature of three selected monitoring points within the drive power system or control system. The required monitoring points can be selected using the monitor select parameters Temperature Monitor Select 1 (07.038), Temperature Monitor Select 2 (07.039) and Temperature Monitor Select 3 (07.052) respectively. The default values give two monitoring points in the power system in Monitored Temperature 1 (07.004) = 01001 and Monitored Temperature 2 (07.005) = 01002, and control board temperature 1 in Monitored Temperature 3 (07.006) = 00001.

The following table shows the value to be entered into the monitor select parameters to select the required monitoring point. If the monitoring point selected does not exist then the monitored temperature is always zero.
| Source | xx | y | zz |
| Control system | 00 | 0 | 01: Control board thermistor 1 |
| Control system | 00 | 0 | 02: Control board thermistor 2 |
| Control system | 00 | 0 | 03: I/O board thermistor (or internal braking resistor in Servo Drive) |
| Control system | 00 | 1 | 00: Inverter thermal model |
| Control system | 00 | 3 | 00: Braking IGBT thermal model |
| Control system | 00 | 4 | 00: Rectifier thermal model |
| Power system | 01 | 0 | zz: Thermistor location defined by zz in the power system |
| Power system | 01 | Rectifier number | zz: Thermistor location defined by zz in the rectifier |
For a multi-module power system the power system measurement that can be selected is shown in the table below. It should be noted that the specific power module cannot be selected and that the highest temperature from each of the power modules is given.
| Source | xx | y | zz |
| Power system | 01 | 0 | 01: U phase power device thermistor |
| Power system | 01 | 0 | 02: V phase power device thermistor |
| Power system | 01 | 0 | 03: W phase power device thermistor |
| Power system | 01 | 0 | 04: General rectifier thermistors |
| Power system | 01 | 0 | 05: General power system thermistor |
| Parameter | 07.005 Monitored Temperature 2 | ||
|---|---|---|---|
| Short description | Displays the temperature set up by Temperature Monitor Select 2 | ||
| Mode | Regeneration | ||
| Minimum | -250 | Maximum | 250 |
| Default | Units | °C | |
| Type | 16 Bit Volatile | Update Rate | Background write |
| Display Format | Standard | Decimal Places | 0 |
| Coding | RO, ND, NC, PT | ||
See Monitored Temperature 1 (07.004) for details.
| Parameter | 07.006 Monitored Temperature 3 | ||
|---|---|---|---|
| Short description | Displays the temperature set up by Temperature Monitor Select 3 | ||
| Mode | Regeneration | ||
| Minimum | -250 | Maximum | 250 |
| Default | Units | °C | |
| Type | 16 Bit Volatile | Update Rate | Background write |
| Display Format | Standard | Decimal Places | 0 |
| Coding | RO, ND, NC, PT | ||
See Monitored Temperature 1 (07.004) for details.
| Parameter | 07.015 Analog Input 3 Mode | ||
|---|---|---|---|
| Short description | Defines the mode of analog input 3 | ||
| Mode | Regeneration | ||
| Minimum | 7 | Maximum | 10 |
| Default | 10 | Units | |
| Type | 8 Bit User Save | Update Rate | Background read |
| Display Format | Standard | Decimal Places | 0 |
| Coding | RW, TE | ||
| Value | Text | Description |
| 7 | Therm Short Cct | Temperature measurement input with short circuit detection |
| 8 | Thermistor | Temperature measurement without short circuit detection |
| 9 | Therm No Trip | Temperature measurement input with no trips |
| 10 | Disabled | Input always zero. This mode is used to disable the current source as the input is on a shared connection with Digital Input 5. |
This parameter defines the possible input modes for analog input 3.
| Parameter | 07.033 Power Output | ||
|---|---|---|---|
| Short description | Instant output power | ||
| Mode | Regeneration | ||
| Minimum | -100.0 | Maximum | 100.0 |
| Default | Units | % | |
| Type | 16 Bit Volatile | Update Rate | 250µs write |
| Display Format | Standard | Decimal Places | 1 |
| Coding | RO, ND, NC, PT | ||
This is an instantaneous power output with fast update rate that is primarily intended to be used as a power feed-forward for applications with a Regen system front end. The full scale (100.0%) value is equal to a power of 3 x (VM_DC_VOLTAGE[MAX] / 2√2) x Full Scale Current Kc (11.061). This is compatible with the power output provided in Unidrive SP and is directly compatible with Power Input 1 (03.010) (and the other power feed-forward parameters) in Regen mode. The scaling is intended to cover the maximum range of likely power in the drive. For example with a 400V 7.5kW drive the full scale d.c. link voltage is 831V and Kc=38.222A, and so the full scale value of this parameter is 3 x (831 / 2√2) x 38.222 = 33.689kW. For Open-loop, RFC-A and RFC-S modes a positive value of power indicates power flowing from the drive to motor. For Regen mode a positive value of power indicates power flowing from the supply to the regen drive.
| Parameter | 07.034 Inverter Temperature | ||
|---|---|---|---|
| Short description | Displays the estimated junction temperature of the hottest power device within the drive inverter | ||
| Mode | Regeneration | ||
| Minimum | -250 | Maximum | 250 |
| Default | Units | °C | |
| Type | 16 Bit Volatile | Update Rate | Background write |
| Display Format | Standard | Decimal Places | 0 |
| Coding | RO, ND, NC, PT | ||
Inverter Temperature (07.034) shows the estimated junction temperature of the hottest power device within the drive inverter. If this temperature exceeds the switch down threshold defined for the power stage the switching frequency is reduced provided this feature has not been disabled (see Auto-switching Frequency Change (05.035)).
| Parameter | 07.035 Percentage Of d.c. Link Thermal Trip Level | ||
|---|---|---|---|
| Short description | Displays the percentage of the maximum allowed temperature as estimated by the thermal model of the d.c. link components | ||
| Mode | Regeneration | ||
| Minimum | 0 | Maximum | 100 |
| Default | Units | % | |
| Type | 8 Bit Volatile | Update Rate | Background write |
| Display Format | Standard | Decimal Places | 0 |
| Coding | RO, ND, NC, PT | ||
Percentage Of d.c. Link Thermal Trip Level (07.035) gives the percentage of the maximum allowed temperature as estimated by the thermal model of the d.c. link components.
| Parameter | 07.036 Percentage Of Drive Thermal Trip Level | ||
|---|---|---|---|
| Short description | Displays the percentage of the thermal trip level of the temperature monitoring point or thermal model in the drive that is highest | ||
| Mode | Regeneration | ||
| Minimum | 0 | Maximum | 100 |
| Default | Units | % | |
| Type | 8 Bit Volatile | Update Rate | Background write |
| Display Format | Standard | Decimal Places | 0 |
| Coding | RO, ND, NC, PT | ||
Percentage Of Drive Thermal Trip Level (07.036) gives the percentage of the thermal trip level of the temperature monitoring point or thermal model in the drive that is highest. This includes all thermal monitoring points (not just those selected by Monitored Temperature 1 (07.004), Monitored Temperature 2 (07.005) and Monitored Temperature 3 (07.006)), Inverter Temperature (07.034) and Percentage Of d.c. Link Thermal Trip Level (07.035).
Percentage Of d.c. Link Thermal Trip Level (07.035) is used directly to give Percentage Of Drive Thermal Trip Level (07.036), but for all other monitored values which are temperatures this is given by Percentage of thermal trip level = (Temperature - 40oC) / (Trip temperature - 40oC) x 100%
The location of the measurement or the thermal model that is related to this temperature is given in Temperature Nearest To Trip Level (07.037). If Percentage Of Drive Thermal Trip Level (07.036) exceeds 90% Drive Over-temperature Alarm (10.018) is set to one. If Percentage Of Drive Thermal Trip Level (07.036) reaches 100% one of the trips given in the table below is initiated. The trip can be reset when the percentage of thermal trip level fall below 95%.
| Temperature | Trip |
| Inverter Temperature (07.034) | OHt Inverter |
| Power system temperature | OHt Power |
| Percentage Of d.c. Link Thermal Trip Level (07.035) | OHt dc Link |
| Control system temperature | OHt Control |
| Parameter | 07.037 Temperature Nearest To Trip Level | ||
|---|---|---|---|
| Short description | Displays the thermistor location or the model that corresponds to the value shown in Percentage Of Drive Thermal Trip Level | ||
| Mode | Regeneration | ||
| Minimum | 0 (Display: 00000) | Maximum | 20999 (Display: 20999) |
| Default | Units | ||
| Type | 16 Bit Volatile | Update Rate | Background write |
| Display Format | Lead Zero Pad | Decimal Places | 0 |
| Coding | RO, ND, NC, PT | ||
Temperature Nearest To Trip Level (07.037) shows the thermistor location or the model that corresponds to the value shown in Percentage Of Drive Thermal Trip Level (07.036) in the form xxyzz as shown in the table below.
| Source | xx | y | zz |
| Control system | 00 | 0 | 01: Control board thermistor 1 |
| Control system | 00 | 0 | 02: Control board thermistor 2 |
| Control system | 00 | 0 | 03: I/O board thermistor (or internal braking resistor in servo Drive) |
| Control system | 00 | 1 | 00: Inverter thermal model |
| Control system | 00 | 2 | 00: D.c. link thermal model |
| Control system | 00 | 3 | 00: Braking IGBT thermal model |
| Control system | 00 | 4 | 00: Rectifier thermal model |
| Power system | 01 | 0 | zz: Thermistor location defined by zz in the power system |
| Power system | 01 | Rectifier number | zz: Thermistor location defined by zz in the rectifier |
| Parameter | 07.038 Temperature Monitor Select 1 | ||
|---|---|---|---|
| Short description | Defines the temperature to be monitored in Monitored Temperature 1 | ||
| Mode | Regeneration | ||
| Minimum | 0 (Display: 00000) | Maximum | 10000 (Display: 10000) |
| Default | 1001 (Display: 01001) | Units | |
| Type | 16 Bit User Save | Update Rate | Background read |
| Display Format | Lead Zero Pad | Decimal Places | 0 |
| Coding | RW | ||
Temperature Monitor Select 1 (07.038) selects the temperature to be monitored in Monitored Temperature 1 (07.004). See Monitored Temperature 1 (07.004) for details.
| Parameter | 07.039 Temperature Monitor Select 2 | ||
|---|---|---|---|
| Short description | Defines the temperature to be monitored in Monitored Temperature 2 | ||
| Mode | Regeneration | ||
| Minimum | 0 (Display: 00000) | Maximum | 10000 (Display: 10000) |
| Default | 1002 (Display: 01002) | Units | |
| Type | 16 Bit User Save | Update Rate | Background read |
| Display Format | Lead Zero Pad | Decimal Places | 0 |
| Coding | RW | ||
Temperature Monitor Select 2 (07.039) selects the temperature to be monitored in Monitored Temperature 2 (07.005). See Monitored Temperature 1 (07.004) for details.
| Parameter | 07.046 Analog Input 3 Thermistor Type | ||
|---|---|---|---|
| Short description | Defines the thermistor type for analog input 3 | ||
| Mode | Regeneration | ||
| Minimum | 0 | Maximum | 1 |
| Default | 0 | Units | |
| Type | 8 Bit User Save | Update Rate | Background read |
| Display Format | Standard | Decimal Places | 0 |
| Coding | RW, TE | ||
| Value | Text | Description |
| 0 | DIN44082 | Three thermistors in series as specified in DIN44082 standard |
| 1 | KTY84 | KTY84 PTC thermistor |
Analog Input 3 Thermistor Type (07.046) defines the operation of the temperature feedback interface for analog input 3 when Analog Input 3 Mode (07.015) is set up for a temperature feedback mode. When a temperature feedback mode is selected a 2mA current source is connected to analog input 3 to supply the temperature feedback device that is connected to the input. DIN44082 and KTY84 devices should always be connected directly to analog input 3. The other devices can be connected directly to analog input 3 if the 2 wire connection option is selected. Alternatively these devices can be used with a 4 wire connection to remove the effect of voltage drops due to the 2mA supply current via the path shown below. If a 4 wire connection is selected analog input 1 is disabled and Analog Input 1 (07.001) always reads as 0.0%. It should be noted that the input system takes account of the input impedance of analogue input 3 when 2 wire mode is used, and of both analogue input 1 and analogue input 3 when 4 wire mode is used. For this reason it is important that 2 wire mode is selected when the connection between Analogue Input 1+ and Analogue input 3 is not present, and that 4 wire mode is selected if the connection is present.

| Parameter | 07.047 Analog Input 3 Thermistor Feedback | ||
|---|---|---|---|
| Short description | Displays the measured resistance of analog input 3 | ||
| Mode | Regeneration | ||
| Minimum | 0 | Maximum | 5000 |
| Default | Units | Ω | |
| Type | 16 Bit Volatile | Update Rate | Background write |
| Display Format | Standard | Decimal Places | 0 |
| Coding | RO, ND, NC, PT | ||
Analog Input 3 Thermistor Feedback (07.047) shows the measured resistance.
| Parameter | 07.048 Analog Input 3 Thermistor Trip Threshold | ||
|---|---|---|---|
| Short description | Defines the thermistor trip threshold for analog input 3 | ||
| Mode | Regeneration | ||
| Minimum | 0 | Maximum | 5000 |
| Default | 3300 | Units | Ω |
| Type | 16 Bit User Save | Update Rate | Background read |
| Display Format | Standard | Decimal Places | 0 |
| Coding | RW | ||
Over-temperature detection becomes active for input 3 if Analog Input 3 Thermistor Feedback (07.047) > Analog Input 3 Thermistor Trip Threshold (07.048). Over-temperature becomes inactive for input 3 if Analog Input 3 Thermistor Feedback (07.047) < Analog Input 3 Thermistor Reset Threshold (07.049). If Analog Input 3 Mode (07.015) is 7 or 8 (i.e. tripping is enabled) a Thermistor.003 trip is initiated. The default values for Analog Input 3 Thermistor Trip Threshold (07.048) and Analog Input 3 Thermistor Reset Threshold (07.049) are the levels specified in the DIN 44082 standard.
| Parameter | 07.049 Analog Input 3 Thermistor Reset Threshold | ||
|---|---|---|---|
| Short description | Defines the thermistor reset threshold for analog input 3 | ||
| Mode | Regeneration | ||
| Minimum | 0 | Maximum | 5000 |
| Default | 1800 | Units | Ω |
| Type | 16 Bit User Save | Update Rate | Background read |
| Display Format | Standard | Decimal Places | 0 |
| Coding | RW | ||
See Analog Input 3 Thermistor Trip Threshold (07.048).
| Parameter | 07.050 Analog Input 3 Thermistor Temperature | ||
|---|---|---|---|
| Short description | Displays the temperature of the device based on the resistance to temperature characteristic for the specified device | ||
| Mode | Regeneration | ||
| Minimum | -50 | Maximum | 300 |
| Default | Units | °C | |
| Type | 16 Bit Volatile | Update Rate | Background write |
| Display Format | Standard | Decimal Places | 0 |
| Coding | RO, ND, NC, PT | ||
If a KTY84, PT100, PT1000 or PT2000 type device is selected for temperature feedback then Analog Input 3 Thermistor Temperature (07.050) shows the temperature of the device based on the resistance to temperature characteristic specified for this device. Otherwise Analog Input 3 Thermistor Temperature (07.050) = 0.0.
| Parameter | 07.052 Temperature Monitor Select 3 | ||
|---|---|---|---|
| Short description | Defines the temperature to be monitored in Monitored Temperature 3 | ||
| Mode | Regeneration | ||
| Minimum | 0 (Display: 00000) | Maximum | 10000 (Display: 10000) |
| Default | 1 (Display: 00001) | Units | |
| Type | 16 Bit User Save | Update Rate | Background read |
| Display Format | Lead Zero Pad | Decimal Places | 0 |
| Coding | RW | ||
Temperature Monitor Select 3 (07.052) selects the temperature to be monitored in Monitored Temperature 3 (07.006). See Monitored Temperature 1 (07.004) for details.