Slot 4 Menu 24 − Profinet Setup

Mode: Regeneration

The Ethernet interface supports the profinet protocol and conforms the profinet specification version 2.1

Profinet option module feature listed below,

1. Number of slots : 64 slots (32 input and 32 output)

2. Identification and Maintenance : I&M0, I&M1, I&M2, I&M3, I&M4

3. Link Layer Discovery Protocol

4. Dynamic configuration change

5. Cyclic data at 1ms rate

 


Parameter4.24.001  Enable Profinet Interface
Short descriptionEnable Profinet Interface
Minimum0Maximum1
Default1Units 
Type1 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW, BU

This parameter is used to enable or disable Profinet functionality.

 

Protocol Mode Sele4.ct


Parameter4.24.002  Reset Profinet
Short descriptionReset Profinet
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRW, NC

This parameter is used to perform a warm reset of the protocol interface. When set and the protocol has reset, the parameter will be reset to zero (Off).


Parameter4.24.003  Profinet Default
Short descriptionProfinet Default
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate RateOn Module reset
Display FormatStandardDecimal Places0
CodingRW, NC

This parameter allows the protocol to be defaulted to factory settings. This includes all of the protocol features, configuration, mappings and stored communication parameters


Parameter4.24.004  Configuration Error
Short descriptionDisplay Profinet Configuration Error
Minimum0Maximum7
Default0Units 
Type8 Bit VolatileUpdate RateOn connect request from PLC
Display FormatStandardDecimal Places0
CodingRO, TE, NC, PT, BU

ValueTextDescription
0No ErrorNo Configuration Error detected
1Input MappingMore than 32 input slots configured
2Output MappingMore than 32 out slots configured
3Data SizeSize given in GSDML and actual size miss match
4Param ConfigParam does not exists
5Slot Not AvailSlot configured in flexible slots and actual fitted slot miss-match
6Read Only ParamRead only param is configured for writing
7Out Of MemoryNot sufficient memory to configure InterOption slots

Value

Text

Description

0

No Error

No Error

1

Input Mapping Error

More than 32 inputs parameters are configured 

2

Output Mapping Error

More than 32 outputs parameters are configured 

3

Data Size Error

Data size given in GSDML is not matching with the actual parameter size

4

Parameter Configuration Error

Parameter given in connect request is either  not found or validation failed


Parameter4.24.005  Cyclic data transfers per second
Short descriptionShowing the Profinet cyclic data transfer rate
Minimum0Maximum65535
Default UnitsMessages/s
Type16 Bit VolatileUpdate RateBackground
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT, BU

This parameter shows the profinet cyclic data transfer rate


Parameter4.24.006  Revision counter
Short descriptionModule Revision Counter
Minimum0Maximum65535
Default Units 
Type16 Bit VolatileUpdate RateOn module reset or save
Display FormatStandardDecimal Places0
CodingRO, ND, PT, BU

Initial value of revision counter is 0.

Revision counter will increment if one of the following action is performed,

-          On drive parameter save

-          On drive parameter default

-          On drive mode change

Criteria to reset the revision counter

-          When it reaches to 65535, it will reset to 0


Parameter4.24.007  Profile ID
Short descriptionProfinet Supported Profinet ID
Minimum0Maximum65535
Default62976Units 
Type16 Bit VolatileUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRO, PT, BU

Supported Profinet ID. By default it is 0xF600


Parameter4.24.008  Installation Date
Short descriptionDate when profinet configured
Minimum0
(Display: 00-00-00)
Maximum311299
(Display: 31-12-99)
Default Units 
Type32 Bit VolatileUpdate RateOn device start or reset
Display FormatDateDecimal Places0
CodingRO, ND, PT, BU

This parameter indicates the date of installation or commissioning of the device.

Installation date will be written by controller and user cannot modify it.


Parameter4.24.009  Profinet Timeout Value
Short descriptionTimeout value
Minimum1Maximum10000
Default100Unitsms
Type16 Bit VolatileUpdate RateConnect Request from PLC
Display FormatStandardDecimal Places0
CodingRO, PT, BU

This parameter defines the time period in which PROFINET must receive a cyclic data from PLC before any specified action is performed.  Default timeout value is 100ms and it will be over written by the PLC when connect request is received. User cannot write the timeout value.


Parameter4.24.010  Profinet Timeout Action
Short descriptionAction on cyclic data timeout
Minimum0Maximum4
Default4Units 
Type8 Bit User SaveUpdate RateOn reset
Display FormatStandardDecimal Places0
CodingRW, TE, PT, BU

ValueTextDescription
0TripTrip drive and raise error
1Send flt valuesSend configured fault values to the output parameters
2Clear outputPLC output parameter will have their values set to zero
3Hold lastHold the last value in output
4No actionNo action

Defines the action when no message is received within the time period specified in Profinet timeout value (S.25.09)

Please note that currently only TRIP option is supported to generate the trip on drive in case of Profinet timeout.

Value

Text

Description

0

Trip

Trip drive and raise error 

1

Send flt values

Write the values specified in the Fault Values menu (25) to the PLC output mappings

2

Clear output

PLC output parameter will have their values set to zero

3

Hold last

Hold the last value in output parameters

4

No action

Same as Hold last


Parameter4.24.011  Destination For Timeout Event
Short descriptionDestination for timout event
Minimum0Maximum4
Default0Units 
Type8 Bit User SaveUpdate RateOn Module reset
Display FormatStandardDecimal Places0
CodingRW, TE, PT, BU

ValueTextDescription
0This slotTrigger event in this slot
1Slot 1Trigger event in slot 1
2Slot 2Trigger event in slot 2
3Slot 3Trigger event in slot 3
4Slot 4Trigger event in slot 4

Value

Text

Description

0

This slot

Trigger event in this slot

1

Slot 1

Trigger event in slot 1

2

Slot 2

Trigger event in slot 2

3

Slot 3

Trigger event in slot 3

4

Slot 4

Trigger event in slot 4

Please note that this version of Profinet does not support PROFINET_TIMEOUT_EVENT_DST


Parameter4.24.012  Profinet Timeout Event Type
Short descriptionEvent type trigger
Minimum0Maximum5
Default0Units 
Type8 Bit User SaveUpdate RateOn power on/reset
Display FormatStandardDecimal Places0
CodingRW, TE, PT, BU

ValueTextDescription
0No EventNo Event
1Trigger EventTrigger module event
2Trigger Event 1Trigger module event 1
3Trigger Event 2Trigger module event 2
4Trigger Event 3Trigger module event 3
5Trigger Event 4Trigger module Event 4

 

Value

Text

Description

0

No event

Trigger event in this slot

1

Trigger Event

Trigger module event

2

Trigger Event 1

Trigger module event 1

3

Trigger Event 2

Trigger module event 2

4

Trigger Event 3

Trigger module event 3

5

Trigger Event 4

Trigger module event 4

Defines the event to trigger when a timeout occur. Profinet Timeout Event Destination (S.25.011) must specify an appropriate consumer (slot option) of the event

Please note that this version of PROFINET does not support PROFINET_TIMEOUT_EVENT_TYPE


Parameter4.24.026  Profinet Input Consistency Enable
Short descriptionProfinet Input Consistency Enable
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateStart-up or Reset
Display FormatStandardDecimal Places0
CodingRW

Value

Text

Description

0

OFF

Consistency is disabled

1

ON

Consistency is enabled


Parameter4.24.027  Profinet Input Consistency Trigger
Short descriptionProfinet Input Consistency Trigger
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateOn startup, Reset
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, BU

By default, cyclic data is read from the drive (or via inter-option communication to an option module) just before it is transmitted to the PLC. If the user wishes to control the sampling of new data (e.g. if an NGA module is putting data into the drive menu 20 parameters and data should not be transmitted until they have all been updated) then input profinet consistency should be enabled and a trigger parameter selected.

 

The following scheme is specified:

·         When input profinet consistency is disabled, new cyclic data is sampled just prior to transmission. The cyclic data gets updated in background task.

·         When input profinet consistency is enabled, the value in the input profinet consistency trigger parameter (specified by #S.25.27) is checked at the beginning of the sampling routine. If it is zero then last set of cyclic data is retransmitted. If the value is non-zero then new data is sampled and transmitted, the trigger parameter value is then set to zero. 

If read consistency is enabled, then at reset or following a power cycle, the value in the trigger parameter is set to zero.

In the slot number of parameter S.25.027,

                If S = 0  means drive,

                If S=1 to 3  means the module in slot 1 to 3,  where “S=4” means factory fit module.


Parameter4.24.028  Profinet Output Consistency Enable
Short descriptionProfinet Output Consistency Enable
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateOn starup, Reset
Display FormatStandardDecimal Places0
CodingRW

Value

Text

Description

0

OFF

Consistency is disabled

1

ON

Consistency is enabled


Parameter4.24.029  Profinet Output Consistency Trigger
Short descriptionProfinet Output Consistency Trigger Parameter
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateOn startup, Reset
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, BU

By default, cyclic data is written to the drive (or via inter-option communication to an option module) just after it is received from the PLC. If the user wishes to control the writing of new data (e.g. if an NGA module is reading data from drive menu 20 parameters and data should only be read when until they have all been updated) then output profinet consistency should be enabled and a trigger parameter selected.

 

The following scheme is specified:

·         When input profinet consistency is disabled, new cyclic data is sampled just prior to transmission. This cyclic data gets updated in background task.

·         When output profinet consistency is enabled, the value in the output profinet consistency trigger parameter (specified by #S.25.29) is checked at the beginning of the writing routine. If it is zero then data is written to the cyclic data destination parameters and the trigger parameter is set to 1. If the value is non zero the new data is discarded.

If write consistency is enabled, then at reset or following a power cycle, the value in the trigger parameter is set to zero.

In the slot number of parameter S.25.029, “S=0” means drive, “S= 1 to 3” means the module in slot 1 to 3, “S=4” means factory fit module.