Slot 4 Menu 25 − Profinet Fault Values

Mode: RFC‑S

These parameters define the fault values to sent to the mapped output parameters when a fault occurs.

This menu contains the parameters used to define the values to be sent to the mapped output destinations when fault values have been configured to be sent after a Profinet timeout event (see Profinet Timeout Action  (4.24.010)Destination For Timeout Event (4.24.011) and Profinet Timeout Event Type (4.24.012)) has occurred.


Parameter4.25.001  Output fault value 1
Short descriptionSets the output fault value for mapping 1
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.002  Output fault value 2
Short descriptionSets the output fault value for mapping 2
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.003  Output fault value 3
Short descriptionSets the output fault value for mapping 3
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.004  Output fault value 4
Short descriptionSets the output fault value for mapping 4
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.005  Output fault value 5
Short descriptionSets the output fault value for mapping 5
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.006  Output fault value 6
Short descriptionSets the output fault value for mapping 6
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.007  Output fault value 7
Short descriptionSets the output fault value for mapping 7
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.008  Output fault value 8
Short descriptionSets the output fault value for mapping 8
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.009  Output fault value 9
Short descriptionSets the output fault value for mapping 9
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.010  Output fault value 10
Short descriptionSets the output fault value for mapping 10
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.011  Output fault value 11
Short descriptionSets the output fault value for mapping 11
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.012  Output fault value 12
Short descriptionSets the output fault value for mapping 12
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.013  Output fault value 13
Short descriptionSets the output fault value for mapping 13
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.014  Output fault value 14
Short descriptionSets the output fault value for mapping 14
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.015  Output fault value 15
Short descriptionSets the output fault value for mapping 15
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.016  Output fault value 16
Short descriptionSets the output fault value for mapping 16
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.017  Output fault value 17
Short descriptionSets the output fault value for mapping 17
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.018  Output fault value 18
Short descriptionSets the output fault value for mapping 18
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.019  Output fault value 19
Short descriptionSets the output fault value for mapping 19
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.020  Output fault value 20
Short descriptionSets the output fault value for mapping 20
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.021  Output fault value 21
Short descriptionSets the output fault value for mapping 21
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.022  Output fault value 22
Short descriptionSets the output fault value for mapping 22
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.023  Output fault value 23
Short descriptionSets the output fault value for mapping 23
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.024  Output fault value 24
Short descriptionSets the output fault value for mapping 24
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.025  Output fault value 25
Short descriptionSets the output fault value for mapping 25
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.026  Output fault value 26
Short descriptionSets the output fault value for mapping 26
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.027  Output fault value 27
Short descriptionSets the output fault value for mapping 27
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.028  Output fault value 28
Short descriptionSets the output fault value for mapping 28
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.029  Output fault value 29
Short descriptionSets the output fault value for mapping 29
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.030  Output fault value 30
Short descriptionSets the output fault value for mapping 30
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.031  Output fault value 31
Short descriptionSets the output fault value for mapping 31
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).


Parameter4.25.032  Output fault value 32
Short descriptionSets the output fault value for mapping 32
Minimum-2147483648Maximum2147483647
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, PROFINET interface reset or PROFINET interface enable
Display FormatStandardDecimal Places0
CodingRW, PT

This parameter defines the value to be sent to the mapped output destination when fault values have been configured to be sent (with Profinet Timeout Action  (4.24.010)).