Menu 7 − Analog I/O

Mode: RFC‑A

Analog Outputs
The update time for analog outputs is 250μs; although the output will only change at the update time defined by the source parameter for the output. The following exceptions apply:

  1. Speed Feedback (03.002) has an update time of 4ms and includes a 16ms window filter. If this parameter is selected as a source for output 2 the update time of the source changes to 250us and the only filter applied is the window filter associated with the position feedback interface (i.e. P1 Feedback Filter (03.042) for the P1 interface). It should be noted that this feature is only provided when the position feedback is from a drive interface and not from an option module.
  2. If either analogue output is set up for current mode then the update time for both analogue outputs is 4ms.

Analog Inputs
The normal update time for the analog inputs is 250us. If a thermistor mode is selected the update time is increased to 4ms. It is possible to insert a filter in each of the analogue inputs using Analog Input 1 Filter Time Constant (07.063) etc. to reduce the effect of noise on the input. Analog Input 1 Fast Update Active (07.026) and Analog Input 2 Fast Update Active (07.027) indicate if fast 250us updating is active for each input.

The diagram below shows the parameter structure for each I/O. See Internal I/O Identifier (11.068) for details of which I/O is present for different I/O options. Not all parameters shown in the diagam below are available in every drive derivative.

 


Parameter07.001  Analog Input 1
Short descriptionDisplays the value of analog input 1
ModeRFC‑A
Minimum-100.00Maximum100.00
Default Units%
Type16 Bit VolatileUpdate Rate250us write
Display FormatStandardDecimal Places2
CodingRO, FI, ND, NC, PT

Each analogue input has a resolution of 15 bits plus sign. The resolution given in Analog Input 1 (07.001) etc. is limited by the resolution of the parameter to 0.01%. However, the resolution is maintained if the input is routed to a parameter with a range equal to or larger than 32768. For example if an input is routed to Analog Reference 1 (01.036) and the maximum speed is greater than or equal to 3276.8rpm the resolution is 0.1rpm. By default no filtering is applied to the inputs, and so general noise will cause the value to change within the range of the noise. If some delay is acceptable it is possible to filter the inputs using Analog Input 1 Filter Time Constant (07.063) to Analog Input 3 Filter Time Constant (07.065).

The inputs can operate in different modes (defined by Analog Input 1 Mode (07.007) for analogue input 1). These modes include voltage, current and thermistor modes. The available modes depend on the hardware configuration and are given in the table below. 

Internal I/O Identifier (11.068) Analogue Input 1 Analogue Input 2 Analogue Input 3
0: Standard Analogue and Digital I/O (M600, M700, M701) Bipolar Voltage, Current Bipolar Voltage, Current Bipolar Voltage, Thermistor
1: Digital I/O (M702) Not present Not present Thermistor, Disabled
2: HVAC Analogue and Digital I/O Unipolar Voltage, Current, Thermistor Unipolar Voltage, Current, Thermistor Not present

The "Input Level" is defined for the different modes in the table below.

Mode Input Level
Voltage (Input Voltage / 10V) x 100.00%
0-20mA (Input Current / 20mA) x 100.00%
20-0mA ((20mA - Input Current) / 20mA) x 100.00%
4-20mA ((Input Current - 4mA) / 16mA) x 100.00%
20-4mA ((20mA - Input Current) / 16mA) x 100.00%
Thermistor (Input resistance / 10kΩ ) x 100%

Analog Input 1 (07.001) is derived as follows:

Limits
A1 is the value after the minimum and maximum limits are applied.

If Analog Input 1 Minimum (07.040) ≥ Analog Input 1 Maximum (07.043) then:
A1 = 0.00% whatever the input level.

If Analog Input 1 Minimum (07.040) < 0.00% and Analog Input 1 Maximum (07.043) > 0.00% then:
A1 = Input Level x (100.00% / Analog Input 1 Maximum (07.043))
A1 is then limited between -100% and +100%.

Otherwise:
Input Level is limited between Analog Input 1 Minimum (07.040) and Analog Input 1 Maximum (07.043)
A1 = [Input Level - Analog Input 1 Minimum (07.040)] x 100.00% / (Analog Input 1 Maximum (07.043) - Analog Input 1 Minimum (07.040))

For thermistor modes it should be noted that Analog Input 1 Minimum (07.040), Analog Input 2 Minimum (07.041) and Analog Input 3 Minimum (07.042) have no effect and that the input resistance is limited between 0 and 5kΩ.


Parameter07.002  Analog Input 2
Short descriptionDisplays the value of analog input 2
ModeRFC‑A
Minimum-100.00Maximum100.00
Default Units%
Type16 Bit VolatileUpdate Rate250us write
Display FormatStandardDecimal Places2
CodingRO, FI, ND, NC, PT

Analog Input 2 (07.002) shows the level of analogue input 2. See Analog Input 1 (07.001) for more information.


Parameter07.003  Analog Input 3
Short descriptionDisplays the value of analog input 3
ModeRFC‑A
Minimum-100.00Maximum100.00
Default Units%
Type16 Bit VolatileUpdate Rate250us write
Display FormatStandardDecimal Places2
CodingRO, FI, ND, NC, PT

Analog Input 3 (07.003) shows the level of analogue input 3.


Parameter07.004  Monitored Temperature 1
Short descriptionDisplays the temperature set up by Temperature Monitor Select 1
ModeRFC‑A
Minimum-250Maximum250
Default Units°C
Type16 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Thermal monitoring is provided within the drive to protect the power stage and the control system from over temperature.

Monitored Temperature 1 (07.004), Monitored Temperature 2 (07.005) and Monitored Temperature 3 (07.006) give an indication of the temperature of three selected monitoring points within the drive power system or control system. The required monitoring points can be selected using the monitor select parameters Temperature Monitor Select 1 (07.038), Temperature Monitor Select 2 (07.039) and Temperature Monitor Select 3 (07.052) respectively. The default values give two monitoring points in the power system in Monitored Temperature 1 (07.004) = 01001 and Monitored Temperature 2 (07.005) = 01002, and control board temperature 1 in Monitored Temperature 3 (07.006) = 00001.

The following table shows the value to be entered into the monitor select parameters to select the required monitoring point. If the monitoring point selected does not exist then the monitored temperature is always zero.

Source xx y zz
Control system 00 0 01: Control board thermistor 1
Control system 00 0 02: Control board thermistor 2
Control system 00 0 03: I/O board thermistor (or internal braking resistor in Servo Drive)
Control system 00 1 00: Inverter thermal model
Control system 00 3 00: Braking IGBT thermal model
Control system 00 4 00: Rectifier thermal model
Power system 01 0 zz: Thermistor location defined by zz in the power system
Power system 01       Rectifier number zz: Thermistor location defined by zz in the rectifier

For a multi-module power system the power system measurement that can be selected is shown in the table below. It should be noted that the specific power module cannot be selected and that the highest temperature from each of the power modules is given.

Source xx y zz
Power system 01       0      01: U phase power device thermistor
Power system 01 0 02: V phase power device thermistor
Power system 01 0 03: W phase power device thermistor
Power system 01 0 04: General rectifier thermistors
Power system 01 0 05: General power system thermistor


Parameter07.005  Monitored Temperature 2
Short descriptionDisplays the temperature set up by Temperature Monitor Select 2
ModeRFC‑A
Minimum-250Maximum250
Default Units°C
Type16 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

See Monitored Temperature 1 (07.004) for details.


Parameter07.006  Monitored Temperature 3
Short descriptionDisplays the temperature set up by Temperature Monitor Select 3
ModeRFC‑A
Minimum-250Maximum250
Default Units°C
Type16 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

See Monitored Temperature 1 (07.004) for details.


Parameter07.007  Analog Input 1 Mode
Short descriptionDefines the mode of analog input 1
ModeRFC‑A
Minimum-4Maximum6
Default6Units 
Type8 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW, TE

ValueTextDescription
-44-20mA Low4-20mA low value on current loss. Analog input level is 0.00% if the current is below 3mA. (Same as 4.20mA setting.)
-320-4mA Low20-4mA low value on current loss. Analog input level is 0.00% if the current is below 3mA. (Same as 20-4mA setting.)
-24-20mA Hold4-20mA hold at level before loss on current loss. Analog input level remains at the value it had in the previous sample before the current fell below 3mA.
-120-4mA Hold20-4mA hold at level before loss on current loss. Analog input level remains at the value it had in the previous sample before the current fell below 3mA.
00-20mA0-20mA
120-0mA20-0mA
24-20mA Trip4-20mA trip on current loss. Analog input level is 0.00% and an 'An Input 1/2 Loss' trip is initiated if the current is below 3mA.
320-4mA Trip20-4mA trip on current loss. Analog input level is 0.00% and an 'An Input 1/2 Loss' trip is initiated if the current is below 3mA.
44-20mA4-20mA no action on loss. Analog input level is 0.00% if the current is below 3mA.
520-4mA20-4mA no action on loss. Analog input level is 0.00% if the current is below 3mA.
6VoltVoltage

This parameter defines the possible input modes for analog input 1.


Parameter07.008  Analog Input 1 Scaling
Short descriptionDefines the scaling factor of analog input 1
ModeRFC‑A
Minimum0.000Maximum10.000
Default1.000Units 
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places3
CodingRW

Analog Input 1 (07.001) is modified by Analog Input 1 Scaling (07.008), Analog Input 1 Offset (07.030) and Analog Input 1 Invert (07.009) before it is routed to its destination as follows:

A1O = Analog Input 1 (07.001) + Analog Input 1 Offset (07.030)

A1O is the value after the offset has been applied and is limited between -100.00% and 100.00%

A1S = A1O x Analog Input 1 Scaling (07.008)

A1S is the value after the scaling and the offset have been applied and is limited between -100.00% and 100.00%

If Analog Input 1 Invert (07.009) = 0 then A1I = A1S otherwise A1I = -A1S

A1I is the value after the invert, scaling and offset have been applied and is the final value that is routed to the destination defined by Analog Input 1 Destination (07.010).


Parameter07.009  Analog Input 1 Invert
Short descriptionInverts the signal for analog input 1
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

See Analog Input 1 Scaling (07.008).


Parameter07.010  Analog Input 1 Destination
Short descriptionDefines the output parameter for analog input 1
ModeRFC‑A
Minimum0.000Maximum59.999
Default1.036Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRW, DE, PT, BU

See Analog Input 1 Scaling (07.008).


Parameter07.011  Analog Input 2 Mode
Short descriptionDefines the mode for analog input 2
ModeRFC‑A
Minimum-4Maximum6
Default6Units 
Type8 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW, TE

ValueTextDescription
-44-20mA Low4-20mA low value on current loss. Analog input level is 0.00% if the current is below 3mA. (Same as 4.20mA setting.)
-320-4mA Low20-4mA low value on current loss. Analog input level is 0.00% if the current is below 3mA. (Same as 20-4mA setting.)
-24-20mA Hold4-20mA hold at level before loss on current loss. Analog input level remains at the value it had in the previous sample before the current fell below 3mA.
-120-4mA Hold20-4mA hold at level before loss on current loss. Analog input level remains at the value it had in the previous sample before the current fell below 3mA.
00-20mA0-20mA
120-0mA20-0mA
24-20mA Trip4-20mA trip on current loss. Analog input level is 0.00% and an 'An Input 1/2 Loss' trip is initiated if the current is below 3mA.
320-4mA Trip20-4mA trip on current loss. Analog input level is 0.00% and an 'An Input 1/2 Loss' trip is initiated if the current is below 3mA.
44-20mA4-20mA no action on loss. Analog input level is 0.00% if the current is below 3mA.
520-4mA20-4mA no action on loss. Analog input level is 0.00% if the current is below 3mA.
6VoltVoltage

This parameter defines the possible input modes for analog input 2.


Parameter07.012  Analog Input 2 Scaling
Short descriptionDefines the scaling factor for analog input 2
ModeRFC‑A
Minimum0.000Maximum10.000
Default1.000Units 
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places3
CodingRW

The scaling, offset and invert functions for analog input 2 are defined in the same way as for analog input 1. See Analog Input 1 Scaling (07.008).


Parameter07.013  Analog Input 2 Invert
Short descriptionInverts the signal for analog input 2
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

The scaling, offset and invert functions for analog input 2 are defined in the same way as for analog input 1. See Analog Input 1 Scaling (07.008).


Parameter07.014  Analog Input 2 Destination
Short descriptionDefines the output parameter for analog input 2
ModeRFC‑A
Minimum0.000Maximum59.999
Default1.037Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRW, DE, PT, BU

The scaling, offset and invert functions for analog input 2 are defined in the same way as for analog input 1. See Analog Input 1 Scaling (07.008).


Parameter07.015  Analog Input 3 Mode
Short descriptionDefines the mode of analog input 3
ModeRFC‑A
Minimum6Maximum9
Default6Units 
Type8 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW, TE

ValueTextDescription
6VoltVoltage
7Therm Short CctTemperature measurement input with short circuit detection
8ThermistorTemperature measurement without short circuit detection
9Therm No TripTemperature measurement input with no trips

This parameter defines the possible input modes for analog input 3.


Parameter07.016  Analog Input 3 Scaling
Short descriptionDefines the scaling factor for analog input 3
ModeRFC‑A
Minimum0.000Maximum10.000
Default1.000Units 
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places3
CodingRW

The scaling, offset and invert functions for analog input 3 are defined in the same way as for analog input 1. See Analog Input 1 Scaling (07.008).


Parameter07.017  Analog Input 3 Invert
Short descriptionInverts the signal of analog input 3
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

The scaling, offset and invert functions for analog input 3 are defined in the same way as for analog input 1. See Analog Input 1 Scaling (07.008).


Parameter07.018  Analog Input 3 Destination
Short descriptionDefines the output parameter for analog input 3
ModeRFC‑A
Minimum0.000Maximum59.999
Default0.000Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRW, DE, PT, BU

The scaling, offset and invert functions for analog input 3 are defined in the same way as for analog input 1. See Analog Input 1 Scaling (07.008).


Parameter07.019  Analog Output 1 Source
Short descriptionDefines the input parameter for analog output 1
ModeRFC‑A
Minimum0.000Maximum59.999
Default3.002Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRW, PT, BU

Analog Output 1 Source (07.019) defines the source parameter for analog output 1. The value of the source parameter is scaled with Analog Output 1 Scaling (07.020) and if the scaling is greater than 1.000 the value is clamped between -100% and +100% or between 0% and 100% depending on whether the output is bipolar or unipolar. The resulting value is then used to control the output. It should be noted that the normal rules for parameter routing do not apply, but the scaling always makes -100% to +100% correspond to the range from minus source parameter maximum to plus source parameter maximum, and 0% corresponds to the source parameter value of zero. This means for example that a parameter with a minimum of 1 and a maximum of 10 will produce an output that changes from 10% to 100% as the parameter is change from minimum to maximum.

The outputs provided with different hardware are given in the table below.

Internal I/O Identifier (11.068) Analogue Output 1 Analogue Output 2
0: Standard Analogue and Digital I/O (M600, M700, M701) Bipolar Voltage Bipolar Voltage
1: Digital I/O (M702) No output No output
2: HVAC Analogue and Digital I/O (F300, F600, H300) Unipolar Voltage or Current Unipolar Voltage or Current


Parameter07.020  Analog Output 1 Scaling
Short descriptionDefines the scaling factor for analog output 1
ModeRFC‑A
Minimum0.000Maximum10.000
Default1.000Units 
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places3
CodingRW

See Analog Output 1 Source (07.019).


Parameter07.022  Analog Output 2 Source
Short descriptionDefines the input source for analog output 2
ModeRFC‑A
Minimum0.000Maximum59.999
Default4.002Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRW, PT, BU

Analog Output 2 Source (07.022) defines the source parameter for analog output 2. The value of the source parameter is scaled with Analog Output 2 Scaling (07.023) and if the scaling is greater than 1.000 the value is clamped between -100% and +100% or between 0% and 100% depending on whether the output is bipolar or unipolar. The resulting value is then used to control the output. It should be noted that the normal rules for parameter routing do not apply, but the scaling always makes -100% to +100% correspond to the range from minus source parameter maximum to plus source parameter maximum, and 0% corresponds to the source parameter value of zero. This means for example that a parameter with a minimum of 1 and a maximum of 10 will produce an output that changes from 10% to 100% as the parameter is change from minimum to maximum.

The outputs provided with different hardware are given in the table below.

Internal I/O Identifier (11.068) Analogue Output 1 Analogue Output 2
0: Standard Analogue and Digital I/O (M600, M700, M701) Bipolar Voltage Bipolar Voltage
1: Digital I/O (M702) No output No output
2: HVAC Analogue and Digital I/O (F300, F600, H300) Unipolar Voltage or Current Unipolar Voltage or Current


Parameter07.023  Analog Output 2 Scaling
Short descriptionDefines the scaling factor for analog output 2
ModeRFC‑A
Minimum0.000Maximum10.000
Default1.000Units 
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places3
CodingRW

See Analog Output 2 Source (07.022).


Parameter07.025  Calibrate Analog Input 1 Full Scale
Short descriptionCalibrates the input level for analog input 1
ModeRFC‑A
Minimum0Maximum1
Default0Units 
Type1 Bit VolatileUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW, NC

For analog input 1, and in voltage mode only, the full scale value used to determine the input level can be changed from 10V by calibrating the input. The calibration process is triggered by setting Calibrate Analog Input 1 Full Scale (07.025) to one. Calibrate Analog Input 1 Full Scale (07.025) is cleared automatically when the calibration process is complete. After calibration the actions are as follows:

Input voltage during calibration Result
V < 1.5V The calibration result is ignored and the full scale is set to 10V. Analog Input 1 Full Scale (07.051) is set to zero.
1.5V < V < 2.5V The calibration result is ignored and the full scale or Analog Input 1 Full Scale (07.051) are not affected.
V > 2.5V The calibration result is used to set full scale and the value is also stored in Analog Input 1 Full Scale (07.051).

It should be noted that Analog Input 1 Full Scale (07.051) is a power-down save parameter, and so the result is automatically retained after power-down.


Parameter07.026  Analog Input 1 Fast Update Active
Short descriptionAnalog Input 1 Fast Update Active
ModeRFC‑A
Minimum0Maximum1
Default Units 
Type1 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Analog Input 1 Fast Update Active (07.026) is one if the destination for analogue input 1 is being updated at the fast rate of 250us.


Parameter07.027  Analog Input 2 Fast Update Active
Short descriptionAnalog Input 2 Fast Update Active
ModeRFC‑A
Minimum0Maximum1
Default Units 
Type1 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Analog Input 2 Fast Update Active (07.027) is one if the destination for analogue input 2 is being updated at the fast rate of 250us.


Parameter07.028  Analog Input 1 Current Loop Loss
Short descriptionDisplays when analog input 1 falls below 3mA
ModeRFC‑A
Minimum0Maximum1
Default Units 
Type1 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

If Analog Input 1 Mode (07.007) is set to any of the 4-20mA or 20-4mA modes and the current falls below 3mA then Analog Input 1 Current Loop Loss (07.028) is set to one. If the current is more than 3mA or any other mode is selected then Analog Input 1 Current Loop Loss (07.028) is set to zero.


Parameter07.029  Analog Input 2 Current Loop Loss
Short descriptionDisplays when analog input 2 falls below 3mA
ModeRFC‑A
Minimum0Maximum1
Default Units 
Type1 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

See Analog Input 1 Current Loop Loss (07.028).


Parameter07.030  Analog Input 1 Offset
Short descriptionDefines the offset of analog input 1
ModeRFC‑A
Minimum-100.00Maximum100.00
Default0.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 1 Scaling (07.008).


Parameter07.031  Analog Input 2 Offset
Short descriptionDefines the offset of analog input 2
ModeRFC‑A
Minimum-100.00Maximum100.00
Default0.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

The scaling, offset and invert functions for analog input 2 are defined in the same way as for analog input 1. See Analog Input 1 Scaling (07.008).


Parameter07.032  Analog Input 3 Offset
Short descriptionDefines the offset of analog input 3
ModeRFC‑A
Minimum-100.00Maximum100.00
Default0.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

The scaling, offset and invert functions for analog input 3 are defined in the same way as for analog input 1. See Analog Input 1 Scaling (07.008).


Parameter07.033  Power Output
Short descriptionInstant output power
ModeRFC‑A
Minimum-100.0Maximum100.0
Default Units%
Type16 Bit VolatileUpdate Rate250µs write
Display FormatStandardDecimal Places1
CodingRO, ND, NC, PT

This is an instantaneous power output with fast update rate that is primarily intended to be used as a power feed-forward for applications with a Regen system front end. The full scale (100.0%) value is equal to a power of 3 x (VM_DC_VOLTAGE[MAX] / 2√2) x Full Scale Current Kc (11.061). This is compatible with the power output provided in Unidrive SP and is directly compatible with Power Input 1 (03.010) (and the other power feed-forward parameters) in Regen mode. The scaling is intended to cover the maximum range of likely power in the drive. For example with a 400V 7.5kW drive the full scale d.c. link voltage is 831V and Kc=38.222A, and so the full scale value of this parameter is 3 x (831 / 2√2) x 38.222 = 33.689kW. For Open-loop, RFC-A and RFC-S modes a positive value of power indicates power flowing from the drive to motor. For Regen mode a positive value of power indicates power flowing from the supply to the regen drive.


Parameter07.034  Inverter Temperature
Short descriptionDisplays the estimated junction temperature of the hottest power device within the drive inverter
ModeRFC‑A
Minimum-250Maximum250
Default Units°C
Type16 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Inverter Temperature (07.034) shows the estimated junction temperature of the hottest power device within the drive inverter. If this temperature exceeds the switch down threshold defined for the power stage the switching frequency is reduced provided this feature has not been disabled (see Auto-switching Frequency Change (05.035)).


Parameter07.035  Percentage Of d.c. Link Thermal Trip Level
Short descriptionDisplays the percentage of the maximum allowed temperature as estimated by the thermal model of the d.c. link components
ModeRFC‑A
Minimum0Maximum100
Default Units%
Type8 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Percentage Of d.c. Link Thermal Trip Level (07.035) gives the percentage of the maximum allowed temperature as estimated by the thermal model of the d.c. link components.


Parameter07.036  Percentage Of Drive Thermal Trip Level
Short descriptionDisplays the percentage of the thermal trip level of the temperature monitoring point or thermal model in the drive that is highest
ModeRFC‑A
Minimum0Maximum100
Default Units%
Type8 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Percentage Of Drive Thermal Trip Level (07.036) gives the percentage of the thermal trip level of the temperature monitoring point or thermal model in the drive that is highest. This includes all thermal monitoring points (not just those selected by Monitored Temperature 1 (07.004), Monitored Temperature 2 (07.005) and Monitored Temperature 3 (07.006)), Inverter Temperature (07.034) and Percentage Of d.c. Link Thermal Trip Level (07.035).

Percentage Of d.c. Link Thermal Trip Level (07.035) is used directly to give Percentage Of Drive Thermal Trip Level (07.036), but for all other monitored values which are temperatures this is given by Percentage of thermal trip level = (Temperature - 40oC) / (Trip temperature - 40oC) x 100%

The location of the measurement or the thermal model that is related to this temperature is given in Temperature Nearest To Trip Level (07.037). If Percentage Of Drive Thermal Trip Level (07.036) exceeds 90% Drive Over-temperature Alarm (10.018) is set to one. If Percentage Of Drive Thermal Trip Level (07.036) reaches 100% one of the trips given in the table below is initiated. The trip can be reset when the percentage of thermal trip level fall below 95%.

Temperature Trip
Inverter Temperature (07.034) OHt Inverter
Power system temperature OHt Power
Percentage Of d.c. Link Thermal Trip Level (07.035) OHt dc Link
Control system temperature OHt Control


Parameter07.037  Temperature Nearest To Trip Level
Short descriptionDisplays the thermistor location or the model that corresponds to the value shown in Percentage Of Drive Thermal Trip Level
ModeRFC‑A
Minimum0
(Display: 00000)
Maximum20999
(Display: 20999)
Default Units 
Type16 Bit VolatileUpdate RateBackground write
Display FormatLead Zero PadDecimal Places0
CodingRO, ND, NC, PT

Temperature Nearest To Trip Level (07.037) shows the thermistor location or the model that corresponds to the value shown in Percentage Of Drive Thermal Trip Level (07.036) in the form xxyzz as shown in the table below.

Source xx y zz
Control system 00 0 01: Control board thermistor 1
Control system 00 0 02: Control board thermistor 2
Control system 00 0 03: I/O board thermistor (or internal braking resistor in servo Drive)
Control system 00 1 00: Inverter thermal model
Control system 00 2 00: D.c. link thermal model
Control system 00 3 00: Braking IGBT thermal model
Control system 00 4 00: Rectifier thermal model
Power system 01 0 zz: Thermistor location defined by zz in the power system
Power system 01           Rectifier number zz: Thermistor location defined by zz in the rectifier


Parameter07.038  Temperature Monitor Select 1
Short descriptionDefines the temperature to be monitored in Monitored Temperature 1
ModeRFC‑A
Minimum0
(Display: 00000)
Maximum10000
(Display: 10000)
Default1001
(Display: 01001)
Units 
Type16 Bit User SaveUpdate RateBackground read
Display FormatLead Zero PadDecimal Places0
CodingRW

Temperature Monitor Select 1 (07.038) selects the temperature to be monitored in Monitored Temperature 1 (07.004). See Monitored Temperature 1 (07.004) for details.  


Parameter07.039  Temperature Monitor Select 2
Short descriptionDefines the temperature to be monitored in Monitored Temperature 2
ModeRFC‑A
Minimum0
(Display: 00000)
Maximum10000
(Display: 10000)
Default1002
(Display: 01002)
Units 
Type16 Bit User SaveUpdate RateBackground read
Display FormatLead Zero PadDecimal Places0
CodingRW

Temperature Monitor Select 2 (07.039) selects the temperature to be monitored in Monitored Temperature 2 (07.005). See Monitored Temperature 1 (07.004) for details. 


Parameter07.040  Analog Input 1 Minimum
Short descriptionDefines the minimum value for analog input 1
ModeRFC‑A
Minimum-100.00Maximum100.00
Default-100.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 1 (07.001).


Parameter07.041  Analog Input 2 Minimum
Short descriptionDefines the minimum value for analog input 2
ModeRFC‑A
Minimum-100.00Maximum100.00
Default-100.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 1 (07.001).


Parameter07.042  Analog Input 3 Minimum
Short descriptionDefines the minimum value for analog input 3
ModeRFC‑A
Minimum-100.00Maximum100.00
Default-100.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 1 (07.001).


Parameter07.043  Analog Input 1 Maximum
Short descriptionDefines the maximum value for analog input 1
ModeRFC‑A
Minimum-100.00Maximum100.00
Default100.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 1 (07.001).


Parameter07.044  Analog Input 2 Maximum
Short descriptionDefines the maximum value for analog input 2
ModeRFC‑A
Minimum-100.00Maximum100.00
Default100.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 1 (07.001).


Parameter07.045  Analog Input 3 Maximum
Short descriptionDefines the maximum value for analog input 3
ModeRFC‑A
Minimum-100.00Maximum100.00
Default100.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 1 (07.001).


Parameter07.046  Analog Input 3 Thermistor Type
Short descriptionDefines the thermistor type for analog input 3
ModeRFC‑A
Minimum0Maximum9
Default0Units 
Type8 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW, TE

ValueTextDescription
0DIN44082Three thermistors in series as specified in DIN44082 standard
1KTY84KTY84 PTC thermistor
2PT100 (4W)PT100 PTC thermistor with 4 wire connection
3PT1000 (4W)PT1000 PTC thermistor with 4 wire connection
4PT2000 (4W)PT2000 PTC thermistor with 4 wire connection
52.0mA (4W)Any device. Full scale equivalent to a resistance of 5k Ohms with 4 wire connection
6PT100 (2W)PT100 PTC thermistor with 2 wire connection
7PT1000 (2W)PT1000 PTC thermistor with 2 wire connection
8PT2000 (2W)PT2000 PTC thermistor with 2 wire connection
92.0mA (2W)Any device. Full scale equivalent to a resistance of 5k Ohms with 2 wire connection

Analog Input 3 Thermistor Type (07.046) defines the operation of the temperature feedback interface for analog input 3 when Analog Input 3 Mode (07.015) is set up for a temperature feedback mode. When a temperature feedback mode is selected a 2mA current source is connected to analog input 3 to supply the temperature feedback device that is connected to the input. DIN44082 and KTY84 devices should always be connected directly to analog input 3. The other devices can be connected directly to analog input 3 if the 2 wire connection option is selected. Alternatively these devices can be used with a 4 wire connection to remove the effect of voltage drops due to the 2mA supply current via the path shown below. If a 4 wire connection is selected analog input 1 is disabled and Analog Input 1 (07.001) always reads as 0.0%. It should be noted that the input system takes account of the input impedance of analogue input 3 when 2 wire mode is used, and of both analogue input 1 and analogue input 3 when 4 wire mode is used. For this reason it is important that 2 wire mode is selected when the connection between Analogue Input 1+ and Analogue input 3 is not present, and that 4 wire mode is selected if the connection is present.


Parameter07.047  Analog Input 3 Thermistor Feedback
Short descriptionDisplays the measured resistance of analog input 3
ModeRFC‑A
Minimum0Maximum5000
Default Units
Type16 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Analog Input 3 Thermistor Feedback (07.047) shows the measured resistance.


Parameter07.048  Analog Input 3 Thermistor Trip Threshold
Short descriptionDefines the thermistor trip threshold for analog input 3
ModeRFC‑A
Minimum0Maximum5000
Default3300Units
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

Over-temperature detection becomes active for input 3 if  Analog Input 3 Thermistor Feedback (07.047) > Analog Input 3 Thermistor Trip Threshold (07.048). Over-temperature becomes inactive for input 3 if  Analog Input 3 Thermistor Feedback (07.047) <  Analog Input 3 Thermistor Reset Threshold (07.049). If Analog Input 3 Mode (07.015) is 7 or 8 (i.e. tripping is enabled) a Thermistor.003 trip is initiated. The default values for Analog Input 3 Thermistor Trip Threshold (07.048) and Analog Input 3 Thermistor Reset Threshold (07.049) are the levels specified in the DIN 44082 standard.


Parameter07.049  Analog Input 3 Thermistor Reset Threshold
Short descriptionDefines the thermistor reset threshold for analog input 3
ModeRFC‑A
Minimum0Maximum5000
Default1800Units
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

See  Analog Input 3 Thermistor Trip Threshold (07.048).


Parameter07.050  Analog Input 3 Thermistor Temperature
Short descriptionDisplays the temperature of the device based on the resistance to temperature characteristic for the specified device
ModeRFC‑A
Minimum-50Maximum300
Default Units°C
Type16 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

If a KTY84, PT100, PT1000 or PT2000 type device is selected for temperature feedback then Analog Input 3 Thermistor Temperature (07.050) shows the temperature of the device based on the resistance to temperature characteristic specified for this device. Otherwise Analog Input 3 Thermistor Temperature (07.050) = 0.0.


Parameter07.051  Analog Input 1 Full Scale
Short descriptionDisplays the full scale value of analog input 1
ModeRFC‑A
Minimum0Maximum65535
Default Units 
Type16 Bit Power Down SaveUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT, BU

See Calibrate Analog Input 1 Full Scale (07.025).


Parameter07.052  Temperature Monitor Select 3
Short descriptionDefines the temperature to be monitored in Monitored Temperature 3
ModeRFC‑A
Minimum0
(Display: 00000)
Maximum10000
(Display: 10000)
Default1
(Display: 00001)
Units 
Type16 Bit User SaveUpdate RateBackground read
Display FormatLead Zero PadDecimal Places0
CodingRW

Temperature Monitor Select 3 (07.052) selects the temperature to be monitored in Monitored Temperature 3 (07.006). See Monitored Temperature 1 (07.004) for details. 


Parameter07.063  Analog Input 1 Filter Time Constant
Short descriptionDefines the time constant of the filter applied to Analogue Input 1.
ModeRFC‑A
Minimum0Maximum6
Default0Units 
Type8 Bit User SaveUpdate RateBackground Read
Display FormatStandardDecimal Places0
CodingRW, TE

ValueText
0Disabled
1500us
21ms
32ms
44ms
58ms
616ms

Unless the analogue input is set up in thermistor mode the update rate is 250us and with this parameter set to its default value no filtering is applied. This parameter can be modified from its default value to apply a first order filter to the input to remove noise. 


Parameter07.064  Analog Input 2 Filter Time Constant
Short descriptionDefines the time constant of the filter applied to Analogue Input 2.
ModeRFC‑A
Minimum0Maximum6
Default0Units 
Type8 Bit User SaveUpdate RateBackground Read
Display FormatStandardDecimal Places0
CodingRW, TE

ValueText
0Disabled
1500us
21ms
32ms
44ms
58ms
616ms

See Analog Input 1 Filter Time Constant (07.063).


Parameter07.065  Analog Input 3 Filter Time Constant
Short descriptionDefines the time constant of the filter applied to Analogue Input 3.
ModeRFC‑A
Minimum0Maximum6
Default0Units 
Type8 Bit User SaveUpdate RateBackground Read
Display FormatStandardDecimal Places0
CodingRW, TE

ValueText
0Disabled
1500us
21ms
32ms
44ms
58ms
616ms

See Analog Input 1 Filter Time Constant (07.063).