Slot 4 Menu 21 − EtherNet/IP In Mappings

Mode: RFC‑A

This menu contains the parameters used to define the source parameters for data that will be transmitted to the PLC.


Parameter4.21.001  Input Mapping Parameter 1
Short descriptionSets input mapping parameter 1
Minimum0Maximum499999
Default10040Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.002  Input mapping parameter 2
Short descriptionSets input mapping parameter 2
Minimum0Maximum499999
Default2001Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.003  Input mapping parameter 3
Short descriptionSets input mapping parameter 3
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.004  Input mapping parameter 4
Short descriptionSets input mapping parameter 4
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.005  Input mapping parameter 5
Short descriptionSets input mapping parameter 5
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.006  Input mapping parameter 6
Short descriptionSets input mapping parameter 6
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.007  Input mapping parameter 7
Short descriptionSets input mapping parameter 7
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.008  Input mapping parameter 8
Short descriptionSets input mapping parameter 8
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.009  Input mapping parameter 9
Short descriptionSets input mapping parameter 9
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.010  Input mapping parameter 10
Short descriptionSets input mapping parameter 10
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.011  Input mapping parameter 11
Short descriptionSets input mapping parameter 11
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.012  Input mapping parameter 12
Short descriptionSets input mapping parameter 12
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.013  Input mapping parameter 13
Short descriptionSets input mapping parameter 13
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.014  Input mapping parameter 14
Short descriptionSets input mapping parameter 14
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.015  Input mapping parameter 15
Short descriptionSets input mapping parameter 15
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.016  Input mapping parameter 16
Short descriptionSets input mapping parameter 16
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.017  Input mapping parameter 17
Short descriptionSets input mapping parameter 17
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.018  Input mapping parameter 18
Short descriptionSets input mapping parameter 18
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.019  Input mapping parameter 19
Short descriptionSets input mapping parameter 19
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.020  Input mapping parameter 20
Short descriptionSets input mapping parameter 20
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.021  Input mapping parameter 21
Short descriptionSets input mapping parameter 21
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.022  Input mapping parameter 22
Short descriptionSets input mapping parameter 22
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.023  Input mapping parameter 23
Short descriptionSets input mapping parameter 23
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.024  Input mapping parameter 24
Short descriptionSets input mapping parameter 24
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.025  Input mapping parameter 25
Short descriptionSets input mapping parameter 25
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.026  Input mapping parameter 26
Short descriptionSets input mapping parameter 26
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.027  Input mapping parameter 27
Short descriptionSets input mapping parameter 27
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.028  Input mapping parameter 28
Short descriptionSets input mapping parameter 28
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.029  Input mapping parameter 29
Short descriptionSets input mapping parameter 29
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.030  Input mapping parameter 30
Short descriptionSets input mapping parameter 30
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.031  Input mapping parameter 31
Short descriptionSets input mapping parameter 31
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.


Parameter4.21.032  Input mapping parameter 32
Short descriptionSets input mapping parameter 32
Minimum0Maximum499999
Default0Units 
Type32 Bit User SaveUpdate RateModule reset, EtherNet/IP interface reset or EtherNet/IP interface enable
Display FormatSlot Menu ParameterDecimal Places0
CodingRW, PT, BU

This parameter defines a source parameter for the data that will be transmitted to the PLC.