Slot 4 Menu 24 Single Line Descriptions − Profinet Setup

Mode: RFC‑A

ParameterRangeDefaultType
4.24.001Enable Profinet Interface Off (0) or On (1)On (1)RWBit   US
4.24.002Reset Profinet Off (0) or On (1)Off (0)RWBit NC  
4.24.003Profinet DefaultOff (0) or On (1)Off (0)RWBit NC  
4.24.004Configuration ErrorNo Error (0), Input Mapping (1), Output Mapping (2), Data Size (3), Param Config (4), Slot Not Avail (5), Read Only Param (6), Out Of Memory (7) No Error (0) ROTxt NCPT 
4.24.005Cyclic data transfers per second0 to 65535 Messages/s RONumNDNCPT 
4.24.006Revision counter0 to 65535  RONumND PT 
4.24.007Profile ID0 to 65535 62976 RONum  PT 
4.24.008Installation Date00-00-00 to 31-12-99  RODateND PT 
4.24.009Profinet Timeout Value 1 to 10000 ms100 msRONum  PT 
4.24.010Profinet Timeout Action Trip (0), Send flt values (1), Clear output (2), Hold last (3), No action (4) No action (4) RWTxt  PTUS
4.24.011Destination For Timeout EventThis slot (0), Slot 1 (1), Slot 2 (2), Slot 3 (3), Slot 4 (4) This slot (0) RWTxt  PTUS
4.24.012Profinet Timeout Event TypeNo Event (0), Trigger Event (1), Trigger Event 1 (2), Trigger Event 2 (3), Trigger Event 3 (4), Trigger Event 4 (5) No Event (0) RWTxt  PTUS
4.24.026Profinet Input Consistency EnableOff (0) or On (1)Off (0)RWBit   US
4.24.027Profinet Input Consistency Trigger0 to 499999 RWNum   US
4.24.028Profinet Output Consistency EnableOff (0) or On (1)Off (0)RWBit   US
4.24.029Profinet Output Consistency Trigger0 to 499999 RWNum   US

RWRead / WriteRORead-onlyBitBit parameterTxtText stringDateDate parameterTimeTime parameter
ChrCharacter parameterBinBinary parameterIPIP addressMacMAC addressVerVersion numberSMPSlot, menu, parameter
NumNumber parameterDEDestinationNDNo default valueRARating dependentNCNon-copyablePTProtected
FIFilteredUSUser savePSPower-down save