| Parameter | Range | Default | Type |
| 05.001 | Output Frequency | VM_SPEED_FREQ_REF[MIN] to VM_SPEED_FREQ_REF[MAX] Hz | RO | Num | ND | NC | PT | FI |
| 05.002 | Output Voltage | VM_AC_VOLTAGE[MIN] to VM_AC_VOLTAGE[MAX] V | RO | Num | ND | NC | PT | FI |
| 05.003 | Output Power | VM_POWER[MIN] to VM_POWER[MAX] kW | RO | Num | ND | NC | PT | FI |
| 05.004 | Motor Rpm | ±180000 rpm | RO | Num | ND | NC | PT | FI |
| 05.005 | D.c. Bus Voltage | VM_DC_VOLTAGE[MIN] to VM_DC_VOLTAGE[MAX] V | RO | Num | ND | NC | PT | FI |
| 05.006 | Rated Frequency | 0.0 to 599.0 Hz | 50Hz: 50.0 Hz 60Hz: 60.0 Hz
| RW | Num | | | | US |
| 05.007 | Rated Current | VM_RATED_CURRENT[MIN] to VM_RATED_CURRENT[MAX] A | 0.000 A | RW | Num | | | | US |
| 05.008 | Rated Speed | 0 to 35940 rpm | 50Hz: 1500 rpm 60Hz: 1800 rpm
| RW | Num | | | | US |
| 05.009 | Rated Voltage | VM_AC_VOLTAGE_SET[MIN] to VM_AC_VOLTAGE_SET[MAX] V | 200V drive: 230 V 400V drive 50Hz: 400 V 400V drive 60Hz: 460 V 575V drive: 575 V 690V drive: 690 V
| RW | Num | | | | US |
| 05.010 | Rated Power Factor | 0.000 to 1.000 | 0.850 | RW | Num | | | | US |
| 05.011 | Number Of Motor Poles | Automatic (0) to 480 (240) Poles | Automatic (0) Poles | RW | Txt | | | | US |
| 05.012 | Auto‑tune | None (0), Basic (1), Improved (2) | None (0) | RW | Txt | | NC | | |
| 05.013 | Dynamic V To F Select | Off (0) or On (1) | Off (0) | RW | Bit | | | | US |
| 05.014 | Open‑loop Control Mode | Ur S (0), Ur (1), Fixed (2), Ur Auto (3), Ur I (4), Square (5) | Ur I (4) | RW | Txt | | | | US |
| 05.015 | Low Frequency Voltage Boost | 0.0 to 25.0 % | 3.0 % | RW | Num | | | | US |
| 05.017 | Stator Resistance | 0.000000 to 1000.000000 Ω | 0.000000 Ω | RW | Num | | | | US |
| 05.018 | Maximum Switching Frequency | 0 to VM_SWITCHING_FREQUENCY kHz | 3 (1) kHz | RW | Txt | | | | US |
| 05.019 | High Stability Space Vector Modulation | Off (0) or On (1) | Off (0) | RW | Bit | | | | US |
| 05.020 | Quasi‑square Enable | Off (0) or On (1) | Off (0) | RW | Bit | | | | US |
| 05.023 | D.c. Bus Voltage High Range | VM_HIGH_DC_VOLTAGE[MIN] to VM_HIGH_DC_VOLTAGE[MAX] V | RO | Num | ND | NC | PT | FI |
| 05.024 | Transient Inductance | 0.000 to 500.000 mH | 0.000 mH | RW | Num | | | | US |
| 05.025 | Stator Inductance | 0.00 to 5000.00 mH | 0.00 mH | RW | Num | | | | US |
| 05.027 | Enable Slip Compensation | Off (0) or On (1) | On (1) | RW | Bit | | | | US |
| 05.031 | Voltage Controller Gain | 1 to 30 | 1 | RW | Num | | | | US |
| 05.035 | Auto‑switching Frequency Change | Enabled (0), Disabled (1), No Ripple Detect (2) | Enabled (0) | RW | Txt | | | | US |
| 05.036 | Auto‑switching Frequency Step Size | 1 to 2 | 2 | RW | Num | | | | US |
| 05.037 | Switching Frequency | 2 (0), 3 (1), 4 (2), 6 (3), 8 (4), 12 (5), 16 (6) kHz | RO | Txt | ND | NC | PT | |
| 05.038 | Minimum Switching Frequency | 0 to VM_MIN_SWITCHING_FREQUENCY kHz | 2 (0) kHz | RW | Txt | | | | US |
| 05.039 | Maximum Inverter Temperature Ripple | 20 to 60 °C | 60 °C | RW | Num | | | | US |
| 05.040 | Spin Start Boost | 0.0 to 10.0 | 1.0 | RW | Num | | | | US |
| 05.042 | Reverse Output Phase Sequence | Off (0) or On (1) | Off (0) | RW | Bit | | | | US |
| 05.059 | Maximum Deadtime Compensation | 0.000 to 10.000 µs | 0.000 µs | RO | Num | | NC | PT | US |
| 05.060 | Current At Maximum Deadtime Compensation | 0.00 to 100.00 % | 0.00 % | RO | Num | | NC | PT | US |
| 05.061 | Disable Deadtime Compensation | Off (0) or On (1) | Off (0) | RW | Bit | | | | US |